Powerware Power Protection Handbook for IBM 9910 International System i and System p Applications
28
E64 Technical Specifications*
Electrical Input
Nominal Voltage 208, 220, 230, and 240 Vac
Input Voltage Ranges 160–288V (without using batteries)
Frequency 50/60 Hz, auto-sensing
Input Power Factor >0.96 in any mode
Frequency Range 50 Hz: 47–53 Hz; 60 Hz: 57–63 Hz
Electrical Output
On Utility Voltage Regulation ±3% of nominal
On Battery Voltage Regulation ±3% of nominal
Efficiency >85% online mode; >90% high-efficiency mode
Frequency Regulation ±3 Hz online; +1 Hz on battery; +3 Hz high-efficiency mode
Load Crest Factor 3 to 1 ratio
Communications
Communication Port
RS-232 communication port standard; optional X-Slot cards available
Communication Cable
Two (2) 6-ft communication cable included (DB-9 to DB-9 and RJ-45 to DB-9)
included
Battery
UPS Internal Battery Type 7 Ah, sealed, maintenance-free lead-acid
EBM Battery Type 9 Ah, sealed, maintenance-free lead-acid
Battery Type Sealed, maintenance-free lead-acid
Battery Runtime See Battery Runtime Chart
Battery Replacement Hot-swappable UPS internal batteries and external batteries modules
Recharge Time <2 hours from complete discharge
Start-On-Battery Allows start of UPS without utility input
General
Topology True online, double-conversion
Diagnostics Full system self-test on power up
UPS Bypass Automatic on overload or UPS failure
Dimensions and Weight See Model Guide
Environmental and Safety
Ambient Operating Temperature 0°C to 40°C (32°F to 104°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Relative Humidity 5% to 90% noncondensing
Heat Dissipation 2066 BTU/hr, maximum
Audible Noise <45 dBA typical; <50 dBA (on battery)
REPO Port Meets NEC code 645-11 intent and UL requirements
Safety Markings UL, cUL, VDE, CE, NOM, NYCE, GS
EMC Compliance FCC-A, VCCI-A, BSMI-A, C-Tick, CE Compliance
Surge Suppression ANSI C62.41 Category B3, and EN61000-4-5 Level 3 Criteria B
* Due to continuing product improvement programs, specifications subject to change without notice.