www.powerware.com/ibm +44 (0) 845 177 3410
31
E65 Technical Specifications*
Electrical Input
Nominal Voltage 200/208, 220, 230, and 240 Vac
Input Voltage Ranges 160–288V
Frequency 50/60 Hz, auto-sensing
Frequency Range 46–54 Hz for 50 Hz; 56–64 Hz for 60 Hz
Electrical Output
On Utility Voltage Regulation -10% to +6% of nominal
On Battery Voltage Regulation ±5% RMS
Voltage Wave Shape (on battery Sine wave
Output Protection Short circuit protection
Battery
Battery Type Sealed, maintenance-free lead-acid
Battery Runtime See Battery Runtime Chart
Battery Replacement Hot-swappable UPS internal batteries and external batteries modules
Recharge Time <3 hours to 90% usable capacity
Start-On-Battery Allows start of UPS without utility input
General
Electrical Power Module
Replacement
Yes, hot-swap
Diagnostics Full system self-test on power up
UPS Bypass Internal bypass
Transfer Time 4 ms typical, 6 ms max
Overload (normal operation) 100-102% indefinite, 103-112% 2 minutes and >112% 12 line cycles
Dimensions and Weight See Model Guide
Communications
User Interface Front control panel
Audible Alarms
For various UPS alarm conditions, including: On Battery, Low Battery, Overload, and
UPS Fault
REPO Port Meets NEC code 645-11 intent and UL requirements
Communication Ports Native USB and serial port
X-Slot Interface Empty; other X-Slot options available
Cable 6-ft communication cable included
Power Management Software Powerware Software Suite CD-ROM (bundled with UPS)
Environmental and Safety
Operating Temperature 10 to 40°C (50 to 104°F)
Storage Temperature -25 to 55°C (-13 to 131°F)
Relative Humidity 0% to 95% noncondensing
Heat Dissipation 2730 BTU/hr, maximum
Lightning & Surge Protection ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5
Surge Energy Rating High-energy 6500A peak
Audible Noise <45 dBA typical
Altitude 3000m (10,000 ft) without derating
Safety Certifications UL; cUL; NOM; C-Tick; CE marking, TUV/VDE, GS
EMC Compliance FCC Part 15, EN50091-2, Class A
* Due to continuing product improvement programs, specifications subject to change without notice.