Table 21. North America cable and fuse sizes.
UL cable and fuse sizes
Output rating Input rating UL application
Input
voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
CT/I
H
current
amps
VT/I
L
current
amps
Recom-
mended
fuse
(Class
J, T, CF,
or CC)
(max.
rating)
100
kAIC
Recom-
mended
miniature
inverse-
time
molded-
case
circuit
breaker
(max.
rating)
10/14
kAIC
Recom-
mended
type
E CMC
(max.
Rating)
65 kAIC
Recom-
mended
inverse-
time
molded-
case
circuit
breaker
(max.
rating)
100 kAIC
(Open type
only for
3-phase)
NEC
wire
size
line
and
motor
AWG
NEC
wire
size
ground
AWG
Terminal
size
line and
motor
AWG
Terminal
size
ground
AWG
380 Vac
to
480 Vac
50/60 Hz
3-phase
FR1 DM1-341D5… 1.5 2.2 1.8 2.6 6 4 XTPR6P3BC1 +
XTPAXLSA or
PKZM0-6.3 +
BK25/3-PKZ0-E
15 14 14 18-8 16-10
DM1-342D2… 2.2 4.3 2.6 5.2 10 8 XTPR6P3BC1 +
XTPAXLSA or
PKZM0-6.3 +
BK25/3-PKZ0-E
15 14 14 18-8 16-10
DM1-344D3… 4.3 5.6 5.2 6.7 15 10 XTPR010BC1 +
XTPAXLSA or
PKZM0-10 +
BK25/3-PKZ0-E
15 14 14 18-8 16-10
DM1-345D6… 5.6 7.6 6.7 9.1 30 15 XTPR010BC1 +
XTPAXLSA or
PKZM0-10 +
BK25/3-PKZ0-E
15 14 10 18-8 16-10
FR2 DM1-347D6… 7.6 12 9.1 14.4 30 20 XTPR016DC1 +
XTPAXLSAD or
PKZM4-16 +
BK50/3-PKZ4-E
20 12 10 20-6 12-8
DM1-34012… 12 16 14.4 19.2 40 25 XTPR025DC1 +
XTPAXLSAD or
PKZM4-25 +
BK50/3-PKZ4-E
30 10 10 20-6 12-8
DM1-34016… 16 23 19.2 27.6 60 32 XTPR032DC1 +
XTPAXLSAD or
PKZM4-32 +
BK50/3-PKZ4-E
40 8 10 20-6 12-8
FR3 DM1-34023.. 23 31 26.5 35.7 70 \ XTPR040DC1 +
XTPAXLSAD or
PKZM4-40 +
BK50/3-PKZ4-E
50 8 8 20-6 10-8
FR4 DM1- 34031… 31 38 35.7 43.7 70 \ XTPR050DC1 +
XTPAXLSAD or
PKZM4-50 +
BK50/3-PKZ4-E
70 6 8 20-2 8-6
DM1-34038… 38 46 43.7 52.9 80 \ XTPR058DC1 +
XTPAXLSAD or
PKZM4-58 +
BK50/3-PKZ4-E
80 4 8 20-2 8-6
525 Vac
to
600 Vac
50/60 Hz
3-phase
FR2 DM1-354D5… 4.5 7.5
DM1-357D5… 7.5 10
DM1-35010… 10 13.5
FR3 DM1-35013… 13.5 18
FR4 DM1-35018… 18 22
DM1-35022… 22 27
Notes:
Can be any UL listed type with below ratings.
Due to UL listing, only can be below Eaton types.
Line and motor cable size is selected according to UL 61800-5-1 for copper conductor rated 75°C. Use only with copper wire rated 75°C here. Size requirements for
other different wire types are defined in the National Electrical Code
®
, ANSI/NFPA
®
70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 61800-5-1.
n If power cubes or bypass are used, a UL listed Class J, T, CF, CC or equivalent fuse is recommended.
Refer to Appendix B for specific branch circuit protection devices types recommended by Eaton.
(continued).