EasyManua.ls Logo

Eaton PowerXL DM1 Series - Page 132

Eaton PowerXL DM1 Series
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
122
Chapter 6 - Pump control application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 46. PI Controller (Cont.).
P7.1.8
b
PI dead band delay
ID 1306
Minimum value:
0.00 s
Maximum value:
320.00 s
Default value:
0.00 s
Description:
If the PI process value goes out of the dead band area for the desired time delay, at that point the controller will re-initialize and try to
level out again.
P7.1.9
b
PI ramp time
ID 1311
Minimum value:
0.00 s
Maximum value:
300.00 s
Default value:
0.00 s
Description:
Defines the rising and falling ramp times for changes in the process value.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.
Table 47. Setpoint (Cont.).
P7.2.1 - Standard.
P7.2 .1.1
b
PI keypad setpoint 1
ID 1307
Minimum value:
PI Process Unit Min
Maximum value:
PI Process Unit Max
Default value:
0.00 varies
Description:
Keypad PI reference value setpoint 1.
P7.2.1.2
b
PI keypad setpoint 2
ID 1309
Minimum value:
PI Process Unit Min
Maximum value:
PI Process Unit Max
Default value:
0.00 varies
Description:
Keypad PI reference value setpoint 2.
P7.2 .1.3
b
PI wake-up action
ID 2466
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Wake-up when below wake-up level.
1 = Wake-up when above wake-up-level.
2 = Wake-up when below wake-up level % from PI setpoint.
3 = Wake-up when above wake-up level %from PI setpoint.
Description:
This parameter defines the wake-up function action.
P7.2.2 - Setpoint 1.
P7.2.2.1
a
PI setpoint 1 source
ID 1312
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Not used;
1 = PI keypad setpoint 1;
2 = PI keypad setpoint 2;
3 = AI;
4 = Drive reference pot;
5 = FB process data input 1;
6 = FB process data input 2;
7 = FB process data input 3;
8 = FB process data input 4;
9 = FB process data input 5;
10 = FB process data input 6;
11 = FB process data input 7;
12 = FB process data input 8;
13 = FB PI setpoint 1; or
14 = FB PI setpoint 2.
Description:
Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or
fieldbus message.
P7.2.2.2
a
PI setpoint 1 sleep enable
ID 1315
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Disabled; or
1 = Enabled.
Description:
This function will disable the output when the frequency drops below the sleep frequency for the sleep delay time. The output
re-engages when feedback rises above the wake-up level.
.