Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES  MN040049EN—September 2021   www.eaton.com
Figure 12.  Bandwidth feedback.
1.  Feedback out of bandwidth, output frequency over staging frequency, start delay counter; delay times out,  
and interlock 2 is OK, add aux. 1 motor by closing its corresponding relay.
2.  As above, add aux. 2 motor.
3.  Aux. 2’s interlock lost, add aux. 3 as backup immediately.
4.  Add aux. 2 motor again since its interlock resumed.
5.  Feedback out of bandwidth, output frequency below de-staging frequency, start delay counter; delay times out,  
remove aux. 2 motor first because it’s the last one which been added.
6.  As above, remove aux. 3 motor.
7.   As above, remove aux. 1 motor.
Interlock  4