Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 62. Protections (Cont.).
P6.1.10
ab
Underload protection
ID 317
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = No response;
1 = Warning;
2 = Fault - stop mode after fault according to parameter stop mode; or
3 = Fault - stop mode after fault always by coasting.
Description:
If fault is set as the function, the drive will stop and activate the fault stage based on the parameter conditions and the monitoring
status of the motor. If the motor torque drops below the Fnom and F0, torque levels for the time limit the protection is enabled.
Deactivating the protection by setting the parameter to 0 will reset the underload time counter to zero.
P6.1.11
ab
Underload Fnom torque
ID 318
Minimum value:
10.0%
Maximum value:
150.0%
Default value:
50.0%
Description:
The torque limit can be set between 10.0 - 150.0 % x TnMotor. This parameter gives the value for the minimum torque allowed when
the output frequency is at or above the field weakening point. If you change P1.6, nominal motor current, this parameter is automatically
restored to the default value.
P6.1.12
b
Underload F0 torque
ID 319
Minimum value:
5.0%
Maximum value:
150.0%
Default value:
10.0%
Description:
The torque limit can be set between 5.00 - 150.00% x TnMotor. This parameter gives value for the minimum torque allowed at zero
frequency. If you change the value of P1.6, nominal motor current, this parameter is automatically restored to the default value.
F0 Torque
Underload Area
Field Weakening
Point V/Hz Ratio
5 Hz
f