13
Chapter 3 - Startup
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021   www.eaton.com
Table 5.  Start-up wizard instructions (Cont.).
P1.6
a
Motor nominal current
ID 486
Minimum value:
DriveNomCurrCT*1/10 A
Maximum value:
DriveNomCurrCT*2 A
Default value:
DriveNomCurrCT
Description:
Motor nominal nameplate full load current. Find this value on the rating plate of the motor.
1410 min
230/400V 4.0/2.3A 
50 Hz
–1
0.75 kW
cos 
 0.67 
Voltage
Current
Motor Nom.
Speed
Motor PF
Frequency
P1.7
a
Motor nominal speed
ID 489
Minimum value:
300 rpm
Maximum value:
20,000 rpm
Default value:
MotorNomSpeedMFG
Description:
Motor nominal nameplate base speed.  Find this value on the rating plate of the motor.
P1.8
a
Motor power factor
ID 490
Minimum value:
0.30
Maximum value:
1.00
Default value:
0.85
Description:
Motor nominal nameplate full load power factor.  Find this value on the rating plate of the motor.
P1.9
a
Motor nominal voltage
ID 487
Minimum value:
180 V
Maximum value:
690 V
Default value:
MotorNomVoltMFG
Description:
Motor nominal nameplate base voltage.  Find this value on the rating plate of the motor.
P1.10
a
Motor nominal frequency
ID 488
Minimum value:
8.00 Hz
Maximum value:
400.00 Hz
Default value:
MotorNomFreqMFG
Description:
Motor nominal nameplate rated frequency.  Find this value on the rating plate of the motor.  This parameter sets the field weakening 
point (P5.1.5) to the same value.
P1.3
b
Acceleration time 1
ID 103
Minimum value:
0.1 s
Maximum value:
3000.0 s
Default value:
20 .0 s
Description:
The time required for the output frequency to accelerate from zero frequency to maximum frequency (P1.2).  When accelerating from 
different frequency levels, the acceleration time will be a fraction of the total ramp time.