Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 68. Fieldbus (FB) status (Cont.).
P10.3.8
b
Standard status word Bit 7 function select
ID 2422
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
8
Options:
0 = Not used;
1 = Ready;
2 = Run;
3 = Fault;
4 = Fault invert;
5 = Warning;
6 = Reversed;
7 = At speed;
8 = Zero frequency;
9 = Frequency limit supervision;
10 = PI supervision;
11 = Torque limit supervision;
12 = Reference limit supervision;
13 = Power limit supervision;
14 = Temperature limit supervision;
15 = Analog input supervision;
16 = Motor current supervision;
17 = Over heat fault;
18 = Overcurrent regular;
19 = Overvoltage regular;
20 = Undervoltage regular;
21 = 4 mA reference fault/warning;
22 = External fault/warning;
23 = Motor thermal protection;
24 = STO fault output;
25 = Control from I/O;
26 = Remote control;
27 = Un-requested rotation direction;
28 = Fire mode;
29 = Damper control;
30 = Valve control;
31 = Jog speed select;
32 = Fieldbus digital input 1;
33 = Fieldbus digital input 2;
34 = DC charge switch close;
35 = Preheat active;
36 = Cold weather active;
37 = PI Sleep
38 = 2nd stage ramp frequency active;
39 = Prime pump active;
40 = Master drive state;
41 = Slave drive state; or
43 = Single drive control.
Description:
This parameter allows for setting one of the RO functions to a status word that then can be read over the communication standard
status word. This also can be viewed in the keypad monitor value M5.3.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.
Table 69. Serial communication (Cont.).
P11.1 - Basic settings.
P11.1.1
a
Serial communication
ID 586
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Modbus RTU;
1 = BACnet MSTP (*DM1 PRO); or
2 = SWD (*DM1 PRO).
Description:
This parameter defines the communication protocol for RS-485.
P11.2 - Modbus RTU.
P11. 2.1
a
Slave address
ID 587
Minimum value:
1
Maximum value:
247
Default value:
1
Description:
This parameter defines the slave address for RS-485 communication.
.