233
Chapter 7- Multi-purpose application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 71. System (Cont.).
P13.1 - Basic settings.
P13.1.1
Language
ID 340
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = English;
1 = English; or
2 = English.
Description:
This parameter offers the ability to control the frequency converter through the keypad in the language of your choice. Currently
available language is English only.
P13.1.2
a
Application
ID 142
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Standard;;
1 = Pump;
2 = Fan; or
3 = Multi-purpose.
Description:
This parameter sets the active application if multiple applications have been loaded.
P13.1.3
a
Parameter sets
ID 619
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = No;
1 = Load factory default parameters;
2 = Reload set 1;
3 = Reload set 2;
4 = Store parameter set 1;
5 = Store parameter set 2;
6 = Reset; or
7 = Reload defaults VM.
Description:
This parameter allows you to reload the factory default parameter values, and to store and load two customized parameter sets.
P13.1.4
Up to keypad (for remote keypad only)
ID 620
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = No; or
1 = Yes (all parameters).
Description:
This function uploads all existing parameter groups to the keypad.
P13.1.5
a
Down from keypad (for remote keypad only)
ID 621
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = No;
1 = All parameters;
2 = All, no motor; or
3 = Application parameters.
Description:
This function downloads one or all parameter groups from the keypad to the drive.
.