26
Chapter 4 - Standard
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 10. Inputs (Cont.).
P2.2.7
b
DI4 function
ID 1807
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
7
Options:
0 = Not used, no action.
1 = IO terminal start signal 1 - when the control source is set to IO terminal, this input when closed will perform the action defined
by P2.1.3.
2 = IO terminal start signal 2 - when the control source is set to IO terminal, this input when closed will perform the action defined
by P2.1.3.
3 = Reverse - when Start/Stop logic is set to 3 start pulse stop pulse, this input will cause the drive to start in the reverse direction.
4 = Ext. fault 1 - when closed, ext. fault 1 will be activated.
7 = Fault reset - when closed, all active faults will be reset.
8 = Run enable - when closed the drive will allow a start command and be in the ready state.
9 = Preset speed B0 - the seven preset speeds are selected via three binary inputs, this is least significant bit in that binary input.
10 = Preset speed B1 - the seven preset speeds are selected via three binary inputs.
11 = Preset speed B2 - the seven preset speeds are selected via three binary inputs, this is most significant bit in that binary input.
16 = Accel./decel. time set - when open, accel./decel. time 1 will be used, when closed accel./decel. time 2 will be used.
19 = Remote control - when closed, the drive will be forced to the remote control place.
20 = Local control - when closed, the drive will be forced to the local control place.
22 = PI controller - when closed, the drive will force the reference source to PI controller output.
23 = PI setpoint select - when open, parameter setpoint 1 is active, when closed, setpoint 2 is active.
24 = Motor interlock 1 - when closed, motor will be enabled to run.
29 = DC brake active - when closed, DC injection braking will be active.
31 = Derag. enable - when closed. The Derag. cycle for pumps will be initiated.
Description:
Defines the function of digital input 4.
P2.3 - Preset speed.
P2.3.1
b
Preset speed 1
ID 105
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
5.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
P2.3.2
b
Preset speed 2
ID 106
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
10.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
P2.3.3
b
Preset speed 3
ID 118
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
15.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
P2.3.4
b
Preset speed 4
ID 119
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
20.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
P2.3.5
b
Preset speed 5
ID 120
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
25.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
P2.3.6
b
Preset speed 6
ID 121
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
30.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.
P2.3.7
b
Preset speed 7
ID 122
Minimum value:
0.00 Hz
Maximum value:
MaxFreq Hz
Default value:
35.00 Hz
Description:
Preset speed is selected with digital inputs using a binary input.