Chapter 4 - Standard
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 12. Drive control (Cont.).
P4 .1.3
b
Keypad stop
ID 114
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Enabled - keypad operation - In this mode, the keypad stop will only operate when the control source is set to keypad.
1 = Always enabled - In this mode, the stop button will always stop the drive regardless of control mode.
Description:
Enabled or always enabled keypad operation.
P4 .1.4
a
Reverse enabled
ID 1679
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Disabled; or
1 = Enabled.
Description:
Enables or disables the reverse motor direction.
P4 .1.5
Change phase sequence motor
ID 2515
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Change disable; or
1 = Change enable.
Description:
This parameter allows for swapping the motor phase output from u, v, w to u, w, v.
P4 .1.6
b
Power up local remote select
ID 1685
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Hold last;
1 = Local control; or
2 = Remote control.
Description:
Selects what control place the drive will start at after power is applied. The default setting will hold the last state that the drive was in
when powered down, selecting Local or Remote will cause the drive to start in that mode regardless of last state.
P4 .1.8
b
Start mode
ID 252
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Ramp - The drive starts from 0 Hz and ramps to the frequency reference value.
1 = Flying start from stop frequency - The drive will catch a spinning motor. This setting searches for the current frequency using the
last operating frequency as a starting point.
2 = Flying start from maximum frequency - The drive will catch a spinning motor. This setting searches for the current frequency using
the maximum operating frequency as a starting point.
Description:
Selects the start mode operation.
P4 .1.9
b
Stop mode
ID 253
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
1
Options:
0 = Coasting - After a stop command, the motor coasts to a stop uncontrolled by the drive.
1 = Ramp - After the stop command, the speed of the motor is decelerated according to the set deceleration parameters.
Description:
Selects the stop mode operation.