37
Chapter 4 - Standard
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 16. Setpoint (Cont.).
P7.2.2.6
b
PI setpoint 1 sleep level
ID 2450
Minimum value:
MinFreqMin Hz
Maximum value:
MaxFreq Hz
Default value:
0.00 Hz
Description:
Defines the level of which the unit value is used to look at to go into the sleep mode. When the unit drops below this level for the sleep
delay time, it will put the drive into the sleep mode.
P7.2.2.7
b
SP1 sleep mode over cycle time
ID 1842
Minimum value:
0
Maximum value:
10
Default value:
0
Description:
Defines the count the drive come in and out of sleep mode. If multiple times done in this time frame, the drive would trip on ”pump over
cycle” fault.
One cycle is defined when the drive transfers from normal mode to sleep mode.
0 value means do not do the sleep over cycle check and clear ”pump over cycle” fault.
P7.2.2.8
b
SP1 sleep mode maximum cycle time
ID 1843
Minimum value:
0 s
Maximum value:
3,600 s
Default value:
300 s
Description:
Defines the maximum time for sleep over cycle checking.
a
Parameter value can only be changed after the drive has stopped.
b
Parameter value will be set to be default when changing macros.
Table 17. Feedback (Cont.).
P7.3.2 - Feedback 1.
P7.3.2.1
a
PI feedback 1 source
ID 1332
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
2
Options:
0 = Not used;
1 = AI;
2 = Drive reference pot;
3 = FB process data input 1; or
11 = FB PI feedback.
Description:
Defines where feedback signal is being fed into the drive, via analog or fieldbus data value.
a
Parameter value can only be changed after the drive has stopped.
Table 18. Serial communication (Cont.).
P11.1 - Basic settings.
P11.1.1
a
Serial communication
ID 586
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0
Options:
0 = Modbus RTU;
1 = BACnet MSTP (*DM1 PRO); or
2 = SWD (*DM1 PRO).
Description:
This parameter defines the communication protocol for RS-485.
P11.2 - Modbus RTU.
P11. 2.1
a
Slave address
ID 587
Minimum value:
1
Maximum value:
247
Default value:
1
Description:
This parameter defines the slave address for RS-485 communication.
.
.