Chapter 5 - Fan control application
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Table 22. Monitor (Cont.).
M5.4
PI output
ID 22
Minimum value:
%
Maximum value:
%
Default value:
%
Description:
PI output.
M5.5
PI status
ID 23
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
N.A.
Options:
0 = Stopped;
1 = Running; or
2 = Sleep mode.
Description:
PI status indication, indicates if drive is stopped, running in PI mode, or in PI sleep mode.
M9 - Multi-monitoring (for remote keypad only).
M9.1
Multi-monitoring
ID 30
Minimum value:
N.A.
Maximum value:
N.A.
Default value:
0, 1, 2.
Description:
Displays any three monitoring values in a single screen. The values are selectable via the keypad menu. Multi-monitor page could
see three lines of monitoring values. Up and down keys can be used to select the row and then hitting the left arrow key will allow for
editing the value then by going up and down.
Table 23. Parameters (Cont.)
P1 - Basic
parameters.
P1.1
b
Minimum frequency
ID 101
Minimum value:
0.00 Hz
Maximum value:
400.00 Hz
Default value:
0.00 Hz
Description:
Defines the lowest frequency at which the drive will operate. This setting will limit other frequency parameter settings.
1 = Fire mode minimum frequency.
2 = Derag.
3 = MPFC staging frequency.
4 = MPFC master fixed frequency.
5 = Prime pump frequency.
6 = Prime pump frequency 2.
P1.2
b
Maximum frequency
ID 102
Minimum value:
0.00 Hz
Maximum value:
400.00 Hz
Default value:
MaxFreqMFG
Description:
Defines the highest frequency at which the drive will operate. This will limit other frequency parameters.
1 = Keypad reference.
3 = Motor potentiometer.
3 = Jog speed.
4 = 2nd stage ramp frequency.
5 = Fire mode minimum frequency.
6 = Derag.
7 = MPFC staging frequency.
8 = MPFC master fixed frequency.
9 = Prime pump frequency.
10 = Prime pump frequency 2.
11 = Preset speed frequency.
12 = Frequency limit value.
13 = Reference limit value.
14 = Speed control_fs2.
15 = Stall frequency limit.
16 = 4 mA fault frequency.
17 = MPFC de-staging frequency.
18 = Pipe fill loss frequency low.
19 = Pipe fill loss frequency high.
20 = Broken pipe frequency limit.
P1.3
b
Accel. time 1
ID 103
Minimum value:
0.1 s
Maximum value:
3,000.0 s
Default value:
20.0 s
Description:
Defines the time required for the output frequency to accelerate from zero frequency to maximum frequency.
.