62 Eaton Tripp Lite Series Cloud Connected UPS Systems User Guide 934859—Rev B
CChhaapptteerr 88 SSppeecciiffiiccaattiioonnss
88..11 PPrroodduucctt SSppeecciiffiiccaattiioonnss
Table 7. Input Characteristics
BC350RNC(AG-075F) BC600RNC(AG-0760) BC850RNC(AG-0761)
Capacity VA/Watts
350 / 210 600/300 850/450
Voltage AC
120 V
AC voltage range
95–145VAC
High line set 145V +/- 5%
High line reset 140V +/- 5%
Low line set 95V +/- 5%
Low line reset 100V +/- 5%
AC amps
3A 5A 7.1A
frequency
50 or 60 Hz +/- 3 Hz (default 60Hz)
AC input protection
(1) Thermal breaker 5A (1) Thermal breaker 7A (1) Thermal breaker 10A
Line efficiency at full load
>97.4% >97.91% >97.20%
Table 8. Output Characteristics
BC350RNC(AG-075F) BC600RNC(AG-0760) BC850RNC(AG-0761)
Nominal output voltage
120V
AC amps out
2.9A (Nom); 3.7A (Max) 5A (Nom) ; 6.3A (Max) 7.1A (Nom); 8.9A (Max)
AC output voltage (Line
Mode)
120V (follows input voltage 95–145VAC)
AC output voltage (Battery
Mode)
120V
Output AC waveform (Line
Mode)
Sine wave (AC Mode)
Output AC waveform
(Battery Mode)
Simulated sine wave (Battery Mode)
Frequency
50 or 60 Hz follows the AC input frequency
Battery cold start is 60Hz only
Transfer time AC to DC
4 ~ 6 ms (Max < 10 ms)
Product Specifications