1- Open the switchgear door.
3- Remove the fuse from the switchgear.
5- Use a screwdriver and loosen the screw.
4- Put the fuse on a table or on the ground.
6- Remove the blown fuse.
2- Insert the handle and turn it anti-clock wise.
9. MV FUSE REPLACEMENT
7- Replace the new fuse.
(make sure that striker pin looks upwards)
8- Tighten the contact screw by screwdriver then use
silicon grease for silicon body.
Ulusoy URING12-24 - LLF - SF Insulated Compact RMU Switchgear with Fuse User Manual May 2020 www.eaton.com 11