Page #9 background imageLoading...
Page #9 background image
9
Instruction Booklet IB131006EN
Effective March 2019
Instructions for installation,
operation, and maintenance of type
VCP-W vacuum circuit breakers
EATON www.eaton.com
Table 3. (ANSI Standards) type VCP-WC extra capability vacuum circuit breaker 5-27 kV rated symmetrical current basis.
Identification Rated voltage
Circuit
breaker
type
Voltage Insulation level
withstand test
Cont-
inuous
current
at
60 Hz
Short circuit current Inter-
rupt-
ing
time
a
Max.
permis
sible
trip-
ping
delay
Transient
recovery
voltage
(RRRV)
c
Capacitor switching ratings Mech-
anical
endur-
ance
No-
load
oper-
ations
Max.
voltage
V
Voltage
range
factor
K
Sym
inter-
rupting
at V
(Isc)
% DC
comp-
onent
(Idc)
Asym.
inter-
rupting
(It)
Closing
&
latching
capa-
bility
Short-
time
current
for 3
sec.
General
purpose
Definite purpose
Power
freq-
uency
(1 min.)
Lighten-
ing
impulse
1.2x50us
Isolated
shunt
capacitor
bank
current
Back to back capacitor
switching
Capacitor
bank
current
Inrush
current
Inrush
freq-
uency
KV rms kV rms kV peak A rms
kA rms
total % kA rms
kA
peak kA rms Cycles Sec. kV / µs A rms A rms
kA
peak kHz
50 VCP-W
40C
5.95 1 24 75 1200
2000
3000
40 75. 58 139 40 3 2 0.9
0.9
0.8
630
e
1000
e
15
18
3.5
2.7
10,000
10,000
5,000
50 VCP-W
50C
5.95 1 24 75 1200
2000
3000
50 57
57
52
64
64
62
139 50 3 2 0.9
0.9
0.8
630
e
1000
e
15
18
3.5
2.7
10,000
10,000
5,000
75 VCP-W
50C
10.3 1 42 95 1200
2000
3000
50 57
57
52
64
64
62
139 50 3 2 0.9
0.9
0.8
630
e
1000
e
15
18
3.5
2.7
10,000
10,000
5,000
150 VCP-W
25C
17.5 1 42 95 1200
2000
3000
25 50
75
75
31
36
36
97
b
25 3 2 0.95
0.9
0.8
600
f
1000
ef
20
18
3.5
2.7
10,000
10,000
5,000
150 VCP-W
40C
17.5 1 42 95 1200
2000
3000
40 75 58 139 40 3 2 0.9
0.9
0.8
630
d
630
d
250
d
630
ef
1000
ef
15
18
3.5
2.7
10,000
10,000
5,000
150 VCP-W
50C
17.5 1 42 95 1200
2000
3000
50 57
57
52
64
64
62
139 50 3 2 0.9
0.9
0.8
630
d
630
d
250
d
630
ef
1000
ef
15
18
3.5
2.7
10,000
10,000
5,000
150 VCP-W
63C
17.5 1 42 95 1200
2000
3000
63 61
61
61
83
83
83
175 63 3 2 1.07
1.07
1.07
200,1600
i
200,1600
i
200,1600
i
7.7
7.7
7.7
465
465
465
10,000
10,000
10,000
270 VCP-W
25C
27 1 60 125 1200
1600
25 75 36 85 25
h
3 2 1.1 400 20 4.2 2,500
270 VCP-W
32C
27 1 60 125 1200
1600
31.5 57 40 97 32
g
3 1 1.1 400 20 4.2 2,500
270 VCP-W
40C
27 1 60 125 1200
1600
40 50 49 104 40
g
3 1 1.1 400 20 4.2 2,500
a
3 cycles
b
Close & latch current for 1200 A Type 150 VCP-W 25C is proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not de-rated.
c
For higher RRRV contact Eaton for more information.
d
Breaker tested to 2700 A single bank switching for momentary load (Thermal derating must consider harmonic content of current waveform).
e
Breaker tested to 1270 A back-to-back switching for momentary load (Thermal derating must consider harmonic content of current waveform)
f
Capacitor switching ratings are proven at 15 kV. For sealed interrupters at high altitudes, switching voltage is not de-rated.
g
1 second
h
2 second
i
C37.04a-2003 class C2 @ 15 kV
Table 4. (IEC-56 Standards
a
) type VCP-W vacuum circuit breaker through 17.5 kV rated symmetrical current basis.
Identification Rated values
Circuit
breaker type
Voltage class Insulation level Normal
current
Short circuit
breaking current
3 second short
time current
Short circuit
making current
Cable charging
breaking amps
Power
frequency
Impulse
withstand
Amperes kA rms kA rms kV peak AmpereskV rms kV rms kV peak
36VCPW-ND25
36VCPW-ND32
3.6
3.6
10
10
40
40
630, 1250
630, 1250
25
31.5
25
31.5
63
79
25
25
72VCPW-ND25
72VCPW-ND32
7.2
7.2
20
20
60
60
630, 1250
630, 1250
25
31.5
25
31.5
63
79
25
25
36VCP-W25
36VCP-W32
36VCP-W40
3.6
3.6
3.6
10
10
10
40
40
40
630, 1250, 2000
1250, 2000
1250, 2000
25
31.5
40
25
31.5
40
63
79
100
25
25
25
72VCP-W25
72VCP-W32
72VCP-W40
7.2
7.2
7.2
20
20
20
60
60
60
630, 1250, 2000
1250, 2000
1250, 2000
25
31.5
40
25
31.5
40
63
79
100
25
25
25
120VCP-W25
120VCP-W32
120VCP-W40
12.0
12.0
12.0
28
28
28
75
75
75
630, 1250, 2000
1250, 2000
1250, 2000
25
31.5
40
25
31.5
40
63
79
100
25
25
25
175VCP-W25
175VCP-W32
175VCP-W40
17.5
17.5
17.5
38
38
38
95
95
95
1250, 2000
1250, 2000
1250, 2000
25
31.5
40
25
31.5
40
63
79
100
31.5
31.5
31.5
a
Interrupting time is 3 cycles at 50/60 Hz. Rated operating sequence 0-3 min- CO-3 min-CO.

Table of Contents

Other manuals for Eaton VCP-W Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton VCP-W Series and is the answer not in the manual?

Eaton VCP-W Series Specifications

General IconGeneral
BrandEaton
ModelVCP-W Series
CategoryCircuit breakers
LanguageEnglish

Related product manuals