Part 10 - Lighting the appliance / First start-up
Parameter
Description
Unit
Default
Min.
Max.
Note
no.
Imperial
(SI)
0
Maximum CH
°C (°F)
80 (176)
20 (68)
85 (185)
temperature
setting
1
Maximum CH
%
100
0
100
power
2
Maximum time for
Minutes
10
0
60
modulation
to full power
3
Pump overrun time
Minutes
1
0,5
C (continues)
Time max. 30 min.
CH
C=Pump continuously
4
Maximum flow
%
100
50
100
pump for CH
operation
5
Minimum flow
%
50
40
100
pump for CH
operation
6
dT Supply/Return
Kelvin
15
5
30
CH operation
7
Outside sensor
0
0
1
0=no outside sensor
present
1=outside sensor
present / weather dependent
control activated
8
K factor for
4
0.5
6
weather-dependent
control
9
K factor for
2
0.5
6
weather-dependent
control night mode
10
Offset outside
K
0
-15
+15
sensor set point
11
Tap water
0/1
0
2
0= Hxx default (No DHW)
configuration
1= Cxx default (Combi)
2= Hxx storage tank operation
12
Required tap water
°C (°F)
61 (142)
40 (101)
70 (158)
temperature
14
Flue gas sensor
2
0
2
0= High limit switch
type
1=NTC
2=High limit switch
and NTC
15
Gas type
1
1
2
1 = Natural gas G20
2 = LPG*.
16
Option print
0
0
99
configuration
17
Anti fast-cycle time
Minutes
2,5
0
10
18
Maximum power
%
100
0
100
DHW
19
0
0
1
Not used.
Do not change.
20
Pressure sensor
0
0
1
0 = activated
de-activated
1 = deactivated
21
Reset to default
0
0
255
111 = reset to factory defaults
values
(requires manual calibration)
Table 10.1Setting parameters
Note: Gas pipe in the boiler needs to be exchanged in the C or H 200 when used on LPG