Part 14 - Troubleshooting
Supply and return switched at installation
CH set point adjusted too low
Max CH modulation set too low
Max modulation time too long
Check speed in diagnose menu (24) and check parameter 4 and 5
Boiler is not able to distribute generated heat
Check installation for sufficient flow
Check heating curve parameters 7,8,9,10
Calibration not completed correctly
Distance / gap electrode not correct
Check electrode gap and distance to burner
Ignition electrode damaged
Replace ignition electrode
Room thermostat connected incorrectly
Check cabling and connection to room thermostat
Opentherm thermostat connected
Set point thermostat (CH temperature) is lower than actual CH temperature. Check item 4 and 5 in
Thermostat does not switch off
Opentherm thermostat connected
Set point thermostat (CH temperature) is higher than actual CH temperature. Check item 4 and 5 in
Main heat exchanger cluttered
Check and clean 3-way valve when required
3-way valve does not change position
Check valve actuator and cables. Replace when required
Readout flow sensor incorrect
Check flow sensor in diagnose menu (07)
Solar tank used to feed boiler
Check availability and setting mixing valve
Setting DHW set point too high
Check DHW temperature via diagnose menu (8) and replace sensor when required
Too high DHW flow over boiler
Check use of correct (and undamaged) flow restrictor
Plate heat exchanger cluttered at CH side
Check plate heat exchanger
Gas pressure regulator stuck or broken, gas valve closed, check grid pressure
Ignition cable broken or not connected
Ignition cable cap damaged
Check for cracks. Replace when required
Ignition transformer damaged
Check if the unit sparks and check the distance and gap of the electrode. If all OK replace burner
Water in ionisation circuit
Check for water (humidity), dry and check operation. Replace when required
Check if valve fully closes when power is unplugged
Exchange sensor and check parameter 14
Wrong setting of temperature limit configuration
Check boiler power and adjust parameter 1 when required
Pump does not run is stuck
Replace pump or try to turn pump shaft.
Check cables for damage and friction free routing
Check sensor positions and connections
Check sensor in diagnose menu (4) and replace when required
Siphon cluttered (condensate cup)
Too high circulation losses or demand
Boiler is not able to heat tank to a temperature above 70C within 3 hours. Check recirculation losses and
Check cables and replace when required.
Check gas valve and replace when required.
Exchange leaking installation part s and refill
Decrease pressure using the drain valve
No temperature rise detected within 1 minute
Check position of supply sensor and flue gas sensor. Check sensor readings via diagnose menu and
after ignition or sensor broken
replace sensor(s) when required
No outdoor sensor connected
Check reading via diagnose menu (11) and replace sensor when required
Check reading via diagnose menu (6) and replace sensor when required
Check supply voltage in standby and operation
Check fan connection to burner control
Too much dust/dirt in fan
Check fan and connection and make dry when required
CH pressure sensor broken
Check reading via diagnose menu (3) and replace when required
Check reading via diagnose menu (7) and replace when required
Incorrect connection to earth
Check earth in supply cable and supply cable connections
No tank nor tank sensor present
Check reading via diagnose menu (12) and replace when required
No code key or faulty connection
Install code key and or check connections
Boiler cannot distribute heat due to high system
Perform calibration with DHW demand to be able to distribute generated heat
Calibration not successfully completed
Perform calibration and check diagnose menu (32)
Check flue pipe for blockages
Change in flue system after calibration
Magnetite filter cluttered
CH return restrainer cluttered
Clean hydro block CH return connection
Resistance in gas supply pipe too high
Check pressure drop over gas supply system too boiler. Contact grid owner when required
CH pressure sensor broken
Replace sensor. When required sensor can be deactivated temporarily. Parameter 20.
Gas / air mixture incorrect
Check fan air intake for cracks and secure placement of the air intake sticker.
Table 14.3 Possible causes and solutions
72