Part 10 - Lighting the appliance / First start-up
Left
Mean value of
Extra information (on the
right)
0
Software version
-
So
1
Heat exchanger mode:
0 rest
2 start fan
3 pre ventilation
4 ignition
5 CH operation
6 DHW operation
7 heat up tap exchanger
8 anti-swing waiting time
2
Modulation level flame + %
Flame + %
-
3
CH pressure
bar
P1
4
CH supply temperature
°C
t1
5
Set point supply temperature
°C
t1 < > SP
CH
6
CH return temperature
°C
t2
7
DHW flow sensor
l / minute
F1
8
DHW temperature
°C
t3
9
Setpoint DHW temperature
°C
t3 < > SP
10
Flue gas temperature
°C
t4
11
Outside temperature
°C
t5
12
Temperature Tank
°C
t6
21
Room temperature (of
°C
rt
OpenTherm® thermostat)
22
Setpoint room temperature
°C
rt < > SP
(of OpenTherm® thermostat)
24
Modulation pump
%
bP
29
Gasvalve modulation current
mA
I = current
30
Flame resistance (actual value)
kOhm
FL = flame
31
Fan speed
rpm
-
32
Calibration done
-
CAL = calibration
completed
33
Flame resistance setpoint 0%
kOhm
FL
34
Flame resistance setpoint ignition speed
kOhm
FL
35
Flame resistance setpoint 100%
kOhm
FL
Table 10.2 Diagnose menu