Operations Manual 31
IRC-3 / ZAS-2 Sensitivity Report
[OP-009.CDR]
Alarm thresholds for 4D, 3D Ion, and Photo sensors are
printed as a % obscuration per foot.
4D is a combination of Ion, Photo and Heat Detectors
3D is a combination of Photo and Heat Detectors
Current device levels :
01 4D Detector 2.5 20
09 Ion Detector 1.4 70
02 4D Detector 2.5 10
15 4D Detector 3.0 80
03 4D Detector 2.5 10
16 4D Detector 2.5 10
04 4D Detector 2.5 30
17 Photo Detector 1.0 50
07 3D Detector 2.0 20
08 Ion Deetctor 0.7 10
Device Device Alarm Maintenance
Address Type Threshold Indicator
= = = = 4D Panel Sensitivity Report = = = =
Date: 11-03-94
Time: 01:10:15
Panel Address: 01
---------------------------------------------------