12 Operations Manual
The system history file is erased upon system Restart. Acknowledge
any alarms by pressing the Next/Ack button. Re-enter the time, date,
and any points previously disabled. Re-enable time controls.
If a ZAS-2 Card is installed in slots P5 and/or P6 of the control panel
motherboard, real-time status information pertaining to the ZAS-2 Card
is displayed:
01:01:01 APXXXX DPXXXX Res0
Com = ZAS-2 Communication Flag
Res = Reset in Progress
Zas = ZAS-2 Internal Trouble
Mpg = ZAS-2 Mapping in Progress
Mpe = Mapping Enabled
Gnd = ZAS-2 Card Ground Fault
Lin = ZAS-2 Class A Fault
Map = ZAS-2 Map Fault
1 = OK (completed)
0 = Fault (in progress)
ENABL/DSABL Button
The ENABL/DSABL button is used to enable or disable system
functions.
Enable
Used to enable a zone, zone message, time control, data line, panel,
action, or sequence.
Notes
1. A level 1 or 2 password is required to disable system functions.
2. Completion of an enable/disable function returns the display back to
the ENABL/DSABL menu shown above. Additional sub-menu
selections can then be made.
Press the ENABL/DSABL button. The display shows the following:
1) Enable 2) Disable
Enter Choice ->_
Key in “1“ (Enable) and press the Enter button. The display shows the
following:
1) Zone 2) Znmsg 3) Tmctrl 4) Datelne 5) Panel
6) Actn 7) Seqnc Enter # Choice->_
Key in the appropriate password and press the Enter button. The
display shows the following:
Enter password level 2 ->_