Operations Manual 11
Notes
1. Changes made to the communications class through this menu
option remain in effect for a maximum of 24 hours.
2. After 24 hours, or upon system RESET, the control panel
automatically reverts to the communications class that was
originally downloaded via the IRC-3 Data Entry Program.
3. This option is useful in troubleshooting a ZAS circuit.
Press the PRGM button. The display shows the following:
1) Load 2) Date 3) Time 4) Password 5) CommAB
6) Restart Enter # Choice ->_
The Test/Prgm LED flashes.
Key in “5“ (Comm AB) and press the Enter button. The display
shows the following:
Panel Address
Enter Choice (pp) ->_
Key in the panel address where the change is to occur and press the
Enter button. The display shows the following:
New Communication Type
Enter Choice (1/2) ->_
Key in “1“ (Class A) or “2” (Class B) and press the Enter button.
The display shows the following:
01:01:01 AP XXXX DP XXXX
Restart
Reboots the system CPU and reloads the system program.
Press the PRGM button. The display shows the following:
1) Load 2) Date 3) Time 4) Password 5) CommAB
6) Restart Enter # Choice ->_
The Test/Prgm LED flashes.
Key in “6“ (Restart) and press the Enter button. The display shows
the following:
Enter password level 2 ->_
Key in your password and press the Enter button. The display shows
the following:
01:01:01 AP 0000 DP 0000