8 Operations Manual
History
Generates a listing of system, circuit, and device history.
• Press the Test/Stat button. The display shows the following:
1) Test 2) Status 3) Sensitivity Report
4) History Enter # Choice ->_
The Test/Prgm LED flashes.
A printer is required to output the history report. The history report will
be printed automatically, regardless of whether the printer is enabled or
disabled.
• Key in “4” (History) and press the Enter button. The display shows
the following:
1) Alarm 2) Security 3) Short 4) Open 5) Alert
6) Verify 7) Watchdog 8) Restore ->_
• Key in the desired category # and press the Enter button. The
display returns to normal.
The history report will output to the printer.
Caution: All History is lost when the system is Restarted or Rebooted.
PRGM Button
The PRGM button is used to load new system data or change existing
data.
Load
Allows the system to receive data from the IRC-3 Data Entry Program.
Note: To gain entry to any programming function, a valid password
must be entered. The passwords installed at the factory are: Level 1 =
1111 and Level 2 = 2222
• Press the PRGM button. The display shows the following:
1) Load 2) Date 3) Time 4) Password 5) CommAB
6) Restart Enter # Choice ->_
The Test/Prgm LED flashes.
• Key in “1“ (Load) and press the Enter button. The display shows the
following:
Enter password level 2 ->_
• Key in the 4-digit password and press the Enter button. The display
shows the following: