vi LaserSense 100 Aspirating Smoke Detector Installers Handbook
smoke tests should be performed to ensure that the farthest sampling hole from
the detector is capable of generating a fire alarm within 120s of receiving smoke.
* The results should be verified at installation by entering the installed detector's
Fire 1 sensitivity (as indicated in the remote software histogram screen) into the
PipeCAD “Options/Calculation options/Detector sensitivity” field and recalculating
the layout results.