Parameterization
Page 66 of 72 MSM-USM2G-BA-UK-004
Delay times / Defluttering
„debounce time“ 0 – 1000 ms
„response delay“ delay time from 0ms .. 32400s (9h), up to 30s in pattern of 1ms,
any longer times in pattern of 1s.
Format: mmm:ss.xxx (xxx indicates the value of the milliseconds).
If no delimiters are used, the entered value will be interpreted in
seconds.
„deflutter number“ 0 – 255
„deflutter time“ 0 – 65535 ms
These fields must not be empty.
Selective functions
For additional parameters, which can be activated or deactivated, the respective function can be
activated by entering “x” or “X” in the corresponding column:
Alarm edges - „rising“, „falling“ (multiple assignment possible)
Collective reports - „collective report1 – collective report3“ (multiple assignment possible)
Horn triggering: - „not active“, „not locked“, „locked“ (only one assignment possible)
Signal source : - „input physical“, „interface“, “display“, „logic“ (only one assignment possible)
For empty fields the respective function is not activated.
6.1.2 IEC-objects of the reporting channels
For each alarm channel and IEC type an IEC object is generated. All objects are formed identically
and have the same parameters.
Discrete object parameters
„ASDU“ - integer value 0 – 65535 or structured xx-xx (e.g. 11-22).
„IOA“ - integer value 0 – 16777215 or structured xx-xx-xx (e.g. 11-22-33).
„IEC-Typ“ - integer value indicating the respective IEC object type according to standard:
1 single report without timestamp
2 single report with short timestamp
3 double report without timestamp
4 double report with short timestamp
5 step position without timestamp
6 step position with short timestamp
7 32 bit report without timestamp
8 32 bit report with short timestamp
30 single report with long timestamp
31 double report with long timestamp
32 step position with long timestamp
33 32 bit report with long timestamp
45 single command without timestamp
46 double command without timestamp
47 step command without timestamp
58 single command with long timestamp
59 double command with long timestamp
60 step command with long timestamp
For empty fields the value will be set to 0 (no type).
Object parameters selective functions
The respective function can be activated by entering “x” or “X” in the corresponding column.
„Link1 –Link4“ - defines on which link the respective object will be forwarded
„blocked“ - the respective object is blocked, no forwarding on the IEC interface
„double“ - the respective object will be addressed as double command
For empty fields the respective function is not activated.