2-10
PRODUCT DATA SHEET
Revision Y05-03 Service Manual - WNG
Model Indoor Unit WNG- 30
Model Outdoor Unit OU8-30 R410A
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr 29000 29000 31800
kW 8.5 8.5 9.08
Power input
(1)
kW 2.92 2.92 2.98
EER (Cooling) or COP(Heating)
(1)
W/W 2.91 2.91 3.05
Energy efficiency class C C D
Power supply V/Ph/Hz 220-240V/Single/50Hz
Rated current A 12.2 12.2 12.1
Starting current A 80
Circuit breaker rating A 25
INDOOR
Fan type & quantity Cross flow x 1
Fan speeds H/M/L RPM 1380/11150/1000
Air flow
(2)
H/M/L m3/hr 1360/1110/1030
External static pressure Min-Max Pa N/A
Sound power level
(3)
H/M/L dB(A) 66/61/57
Sound pressure level
(4)
H/M/L dB(A) 52/48/44
Moisture removal l/hr 3.5
Condensate drain tube I.D mm 16
Dimensions WxHxD mm 1200X340X236
Weight kg 17.0
Package dimensions WxHxD mm 1300/430/315
Packaged weight kg 24.0
Units per pallet units 12
Stacking height units 6 levels
OUTDOOR
Refrigerant control Capillary
Compressor type, model Rotary
Fan type & quantity Axial & 1
Fan speeds H/L RPM 850
Air flow H/L m3/hr 3150
Sound power level H/L dB(A) 69
Sound pressure level
(4)
H/L dB(A) 59
Dimensions WxHxD mm 900X860X340
Weight kg 78
Package dimensions WxHxD mm 985X907X435
Packaged weight kg 82
Units per pallet Units 6
Stacking height units 2 levels
Refrigerant type R410A
Refrigerant charge less distance kg/m 2.42 / 15
Additional charge gr/m 30
Connections between
units
Liquid line In.(mm) 3/8”
Suction line In.(mm) 5/8”
Max.tubing length m. 30
Max.height
difference
m. 15
Operation control type LCD Remote control
Heating elements kW
Others Crankcase heater (50W),
(1)
Rating conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit.