Service Manual
WMZ Series
REFRIGERANT
R407C
R22
COOLING ONLY
HEAT PUMP
SEPTEMBER 2005
Indoor Units Outdoor Units
WMZ 7 GCZ 7
WMZ 9 GCZ 9
WMZ 12 GCZ 12
WMZ 17 GCZ 17
WMZ 22 GCZ 24

Questions and Answers

  • J
    Jesse ReynoldsAug 19, 2025
    Why is my Electra Wmz 9 not cooling or heating, and only the indoor fan works?
    • E
      Ebony KaneSep 12, 2025
      If your Electra Air Conditioner's indoor fan is running but there's no cooling or heating, the outdoor fan motor may be faulty, or another issue might have triggered the compressor overload protection. Try removing any obstructions blocking the outdoor fan. If that doesn't work, the P.C.B. may need replacement.
  • R
    Rachel LeeAug 21, 2025
    What to do if my Electra Wmz 9 Air Conditioner is not cooling or heating, but the indoor fans are working?
    • S
      Sean HarperAug 21, 2025
      If your Electra Air Conditioner's indoor fans are working, but there is no cooling or heating, the overload safety device on the compressor may have cut out due to low voltage or high temperature, the compressor run capacitor could be faulty, or the compressor windings may be shorted. Check for proper voltage, switch off the power, and try again after one hour. You may also need to replace the compressor capacitor or the compressor.
  • P
    Pam WoodsAug 23, 2025
    What to do if my Electra Wmz 9 is in heat mode but operating in cooling?
    • P
      pjacobsAug 23, 2025
      If your Electra Air Conditioner is set to heat mode but is operating in cooling, the RV coil may be faulty, or the valve may be stuck. Replace the RV coil or the reversing valve.
  • J
    Justin KleinAug 26, 2025
    Why is my Electra Wmz 9 outdoor fan not working correctly?
    • K
      kellymoonAug 26, 2025
      If the outdoor fan on your Electra Air Conditioner isn't functioning properly, check the voltage between the outdoor fan terminals on the main P.C.B. If there's no voltage, replace the main P.C.B. If there is voltage, replace the capacitor or motor. Also, check and repair the electrical wiring between the indoor and outdoor units.
  • M
    Marcus MillsAug 27, 2025
    Why is my Electra Wmz 9 Air Conditioner only running the indoor fan?
    • E
      Edward DanielsAug 27, 2025
      If your Electra Air Conditioner is only running the indoor fan, the run capacitor of the outdoor fan motor may be faulty, or the windings of the outdoor fan may be shorted. Replace the capacitor or the motor.
  • R
    Renee DanielAug 29, 2025
    Why is my Electra Air Conditioner indoor fan not functioning correctly?
    • U
      usnowAug 30, 2025
      If the indoor fan of your Electra Air Conditioner isn't working correctly, check the voltage between the indoor fan terminals on the main P.C.B. If there is voltage, replace the capacitor or motor.
  • N
    Nichole VelazquezAug 31, 2025
    What to do if my Electra Wmz 9 Air Conditioner compressor does not start up?
    • T
      Travis JohnsonSep 1, 2025
      If the compressor on your Electra air conditioner isn't starting, begin by checking the voltage at the compressor terminals on the outdoor unit using an ammeter. If there's no voltage, the main P.C.B. may need to be replaced. If the voltage is low, repair the power supply. If the voltage is correct, consider replacing the capacitor or the compressor itself. If there is no voltage, repair electrical wiring between indoor and outdoor units.
  • A
    Andrea MolinaSep 3, 2025
    What to do if water accumulates and overflows from my Electra Air Conditioner indoor unit?
    • J
      Judy HansenSep 3, 2025
      If water is accumulating and overflowing from the indoor unit of your Electra Air Conditioner, the drain tube or spout of the drain pan is likely clogged. Disassemble the plastic drain tube from the spout of the indoor unit drain pan to clear the blockage.
  • T
    Timothy BellSep 5, 2025
    Why is my Electra Wmz 9 Air Conditioner only running the indoor fan and compressor?
    • F
      fitzgeraldtinaSep 5, 2025
      If your Electra Air Conditioner is only running the indoor fan and compressor, the outdoor fan may be blocked. Remove any obstructions.
  • E
    Elizabeth EllisSep 7, 2025
    What to do if my Electra Wmz 9 Air Conditioner has freeze-up of outdoor coil in heating mode?
    • K
      Kristie MitchellSep 7, 2025
      If you notice freeze-up of the outdoor coil in heating mode on your Electra Air Conditioner, resulting in a poor heating effect while the indoor fan operates, the outdoor thermistor could be faulty, the control cable might be damaged, the outdoor temperature may be below design conditions, or the outdoor unit air outlet might be blocked. Replace the thermistor or repair the control cable. If the outdoor temperature is too low, shut the unit off as it cannot work properly. Also, ensure there are no obstructions blocking the outdoor unit air outlet.

Electra Wmz 9 Specifications

General IconGeneral
BrandElectra
ModelWmz 9
CategoryAir Conditioner
LanguageEnglish