2-13
PRODUCT DATA SHEET
Revision Y05-03
Service Manual - WNG
Model Indoor Unit WNG 36
Model Outdoor Unit OU10-36T
Installation Method of Pipe Flared
Characteristics Units Cooling Only Cooling Heating
Capacity
(1)
Btu/hr 35480 35480 38200
kW 10.40 10.40 11.20
Power input
(1)
kW 3.06 3.06 3.40
EER (Cooling) or COP(Heating)
(1)
W/W 3.40 3.40 3.30
Energy efficiency class A A C
Power supply V/Ph/Hz 400V/3/50Hz
Rated current A 3X6.3 3X6.3 3X7.2
Starting current A 43
Circuit breaker rating A 3X16
INDOOR
Fan type & quantity Cross flow x 1
Fan speeds H/M/L RPM 1380/1270/1150
Air flow
(2)
H/M/L m3/hr 1360/1240/1110
External static pressure Min-Max Pa 0
Sound power level
(3)
H/M/L dB(A) 66/63/61
Sound pressure level
(4)
H/M/L dB(A) 52/50/48
Moisture removal l/hr 4
Condensate drain tube I.D mm 16
Dimensions WxHxD mm 1200x340x236
Weight kg 17
Package dimensions WxHxD mm 1300x430x315
Packaged weight kg 24
Units per pallet units 12 units per pallet
Stacking height units 6 levels
OUTDOOR
Refrigerant control Capillary tube
Compressor type, model Rotary, Mitsubishi Siam NN40VCAMT
Fan type & quantity Propeller(direct) x 2
Fan speeds H/L RPM 1150
Air flow H/L m3/hr 4150
Sound power level H/L dB(A) 70.4
Sound pressure level
(4)
H/L dB(A) 61.1
Dimensions WxHxD mm 900x970x340
Weight kg 87
Package dimensions WxHxD mm 985x1020x435
Packaged weight kg 91
Units per pallet Units 6
Stacking height units 2 levels
Refrigerant type R410A
Refrigerant chargless distance kg/m 2.38kg/15m
Additional charge per 1 meter g/m 30
Connections between
units
Liquid line In.(mm) 3/8”(9.53)
Suction line In.(mm) 3/4”(19.06)
Max. tubing length m. Max.50
Max. height
difference
m. Max.25
Operation control type Remote control
Heating Elements kW
Others Crankcase Heater (50w)
(1)
Rating conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511.
(2)
Airflow in ducted units; at nominal external static pressure.
(3)
Sound power in ducted units is measured at air discharge.
(4)
Sound pressure level measured at 1 meter distance from unit