5-27
PERFORMANCE DATA & PRESSURE CURVES
Revision Y05-03
Service Manual - WNG
5.21 Pressure Curves.
5.21.1 Cooling.
Suction Pressure VS.Outdoor Temp
5
6
7
8
9
10
11
12
15 20 25 30 35 40 46
Outdoor Temp.(DB
o
C )
Suction Pressure (Bar[g])
21/15(DB/WB ºC)
24/17(DB/WB ºC)
27/19(DB/WB ºC)
29/21(DB/WB ºC)
32/23(DB/WB ºC)
Discharge Pressure VS.Outdoor Temp
14
16
18
20
22
24
26
28
30
32
34
36
38
40
15 20 25 30 35 40 46
Outdoor Temp.(DB
o
C )
Discharge Pressure (Barg])
21/15(DB/WB ºC)
24/17(DB/WB ºC)
27/19(DB/WB ºC)
29/21(DB/WB ºC)
32/23(DB/WB ºC)