EasyManua.ls Logo

Electronics Line iconnect - 7.7. Service Menu

Electronics Line iconnect
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Devices
iConnect
Installation Manual
37
Figure 7-2: Wired Zone Menu
7.3.1. Zone Type
The zone type defines the type of alarm the system generates when the detector is tripped.
To program a zone type:
1. From the Programming menu, select Devices, Zones [911].
2. Select the detector you want to program.
3. From the detector’s sub-menu, select Zone Type [#02].
4. Select one of the following zone types:
Normal
Entry/Exit
Follower
Panic
Medical
Fire
24H
24Hr-X (future option)
Gas
Flood
Environmental
No Motion
Arm/Disarm
Crash and Smash
Not Used
For a detailed explanation on the function of each zone type, see p. 133, Appendix E: Zone Types.
7.3.2. Arm Set
The Arm Set option allows you to define the arm methods in which the zone is included.
Each zone can be assigned to Full Arming and/or to Part and/or Perimeter Arming in any combination.
To program the Arm Set option:
1. From the Programming menu, select Devices, Zones [911].
2. Select the zone you want to program.
3. From the zone’s sub-menu, select Arm Set [#03]; the zone’s current Arm Set setting is displayed.
Table 7-1: Arm Set Options
Arm Set Description
1 (F) The zone is included in Full arming.
2 (P) The zone is included in Part arming.
3 (PE) The zone is included in Perimeter arming.
4. Use the keys 1, 2 and 3 to toggle the current setting.
It is not necessary to program this option for Panic, Medical, Emergency, Fire, 24Hr, Gas,
Flood and Environmental zones.
7.3.3. Descriptor
For information on device descriptor editing, see p. 35, 7.1 Device Descriptors.

Table of Contents

Other manuals for Electronics Line iconnect

Related product manuals