For the M&G venting installation guide or power venting installation manuals
please visit the link below.
• Only the 5” x 8” direct vent components from M&G DuraVent are approved for use with these replaces. Any of the M&G
DuraVent 5” x 8” direct vent components suitable for the local condition are permitted. Please visit www.europeanhome.com/
qr-support or via the QR code below for installation instructions.
• This replace is shipped with a North American venting adapter. It MUST attach to the vent collar of the replace.
• All venting measurements are taken from the top center of the vent collar on the top of the replace and all congurations
must fall within the acceptable range of the venting charts.
• When using wall terminations no more than (3) 45° or 90° elbows are permitted. See the HORIZONTAL TERMINATIONS section.
• When using vertical terminations no more than (4) 90° elbows OR (8) 45° elbows OR a combination totaling no more than 360
‘elbow degrees’. For example, a combination of (2) 90° elbows and (2) 45° elbows is allowed (90° + 90° + 45°+ 45° equals 270°)
but a combination of (3) 90° elbows and (3) 45° elbows is not allowed (the total equals 405°.) These elbows can be installed
either horizontally or vertically.
• A minimum clearance of 3”/75 mm must be maintained between combustible materials and the top of any horizontal vent
pipe surface; a minimum clearance of 1”/25 mm must be maintained between combustible materials and any other vent pipe
surface.
• The horizontal parts of the venting must be pitched up away from the replace. For every 12” / 305 mm of horizontal run, the
venting must rise ¼” ⁄ 6.5 mm toward the termination. The venting must never run downward unless with the use of a power
vent.
• Whenever venting passes through a wall, an approved heat shield or ‘wall thimble’ must be installed.
• A power vent system is available. Refer to the appropriate power vent manual for any venting conguration which is outside
of the vent graphs shown here.
• Your venting needs to be inspected annually, including any connected components, to ensure that the system is working as
designed.
CONFIGURING THE VENTING
The replaces in this manual are direct vent replaces that use a co-axial or “pipe within a pipe” venting system. The outer “pipe” or vent
conducts fresh, outside air into the replace and the inner vent carries the exhaust outside. This system, which can run either horizontally
through a side wall or vertically through the roof, produces an ecient system because conditioned building air is not used for combustion.
All of the following points apply to every installation:
• Without a power vent, the maximum allowable rise is 36’/11.0 m and the maximum allowable run is 16’5”/5.0 m but not in
combination.
• Without a power vent, the minimum vent conguration is a 19”/500 mm vertical rise to a 90° elbow plus a 19”/500 mm
horizontal run to a wall termination.