TABLE OF PARAMETERS
PAR.
Liv. DESCRIPTION
SEt
Temperature SEtpoint.
COMPRESSOR
diF 1&2
diFferential. Relay compressor tripping differential. The compressor stops on reaching the
Setpoint value (as indicated by the adjustment probe), and restarts at temperature value equal
to the Setpoint plus the value of the differential. Note: the value 0 cannot be assumed
HSE 1&2
Higher SEt. Maximum possible setpoint value.
LSE 1&2
Lower SEt. Minimum possible setpoint value.
OSP 2
Offset Set Point. Temperature Value to be added to the Set-Point if reduced set is enabled
(Economy function).
dOd 2
digital (input) Open door. Digital input that allow you to switch off loads.
Valid if H11 = ±4 (door switch). n = does not switch off loads; y = switch off loads.
dAd 2
digital (input) Activation delay. Delay time in activating the digital input.
Ont 2
ON time (compressor). Compressor activation time in the event of faulty probe. If OFt=1 and
Ont=0, the compressor is always off, while if OFt=1 and Ont>0 it operated in duty cycle mode.
OFt 2
OFF time (compressor). Compressor deactivation time if probe is faulty. If Ont=1 and
OFt=0, the compressor is always on, while if Ont=1 and OFt>0 it operated in duty cycle mode.
dOn 2
delay (at) On compressor. Delay time in activating the compressor relay after switch-on of
instrument.
dOF 2
delay (after power) OFF. Delay after switch off; the indicated time must elapse between switch-
off of the compressor relay and the successive switch-on.
dbi 2
delay between power-on. Delay between switch-ons; the indicated time must elapse between
two successive switch-ons of the compressor.
OdO (!) 2
delay Output (from power) On. Delay time in activating the outputs after switch-on of the
instrument or after a power failure.