PAR. DESCRIPTION RANGE App1 App2 App3 App4 M.U.
COMMUNICATION (“Addfolder)
PtS Communication protocol selection. t = Televis; d = Modbus. t/d t t t t flag
dEA Index of the device inside the family (valid values from 0 to 14). 0 ... 14 0 0 0 0 num
FAA Device family - valid values from 0 to 14. 0 ... 14 0 0 0 0 num
Pty Modbus parity bit. n = none; E = even; o = odd. n/E/o n n n n num
StP Modbus stop bit. 1b/2b 1b 1b 1b 1b flag
DISPLAY (‘diS’ folder)
LOC
Basic commands modification lock. It is still possible to enter parameter programming
mode and modify them. y = yes; n = no.
n/y
n n n n
flag
PS1 PAssword1: if PS1≠0 is the access key to "User" parameters. 0 ... 250 0 0 0 0 num
PS2 PAssword2: if PS2≠0 is the access key to "Installer" parameters. 0 ... 250 15 15 15 15 num
ndt Display with decimal point. y = yes; n = no. n/y y y y y flag
CA1 Calibration 1. Temperature value to be added to the Pb1 value. -12,0...12,0 0,0 0,0 0,0 0,0 °C/°F
CA3 Calibration 3. Temperature value to be added to the Pb3 value. -12,0...12,0 0,0 0,0 0,0 0,0 °C/°F
ddL
Display mode during defrost.
0= display temperature recorded by Pb1;
1= lock recorded Pb1 value at the start of the defrost cycle; 2= display the “dEF” label.
0/1/2 0 0 0 0 num
Ldd Timeout value for display unlock - dEF label 0 ... 255 30 30 30 30 min
dro
Select the unit of measurement used when displaying the temperature recorded by the
probes. (0 = °C, 1 = °F).
NOTE: switching between °C and °F or vice-versa DOES NOT modify the SEt,
diF values, etc. (e.g. Setpoint=10°C becomes 1F)
0/1 0 0 0 0 flag
ddd
Selects type of value to display.
0 = Setpoint; 1 = probe Pb1; 2 = probe Pb2; 3 = probe Pb3
0/1/2/3 1 1 1 1 num
HACCP (“HCP” folder)
SHH Maximum HACCP alarm signals threshold. -55,0...150
0,0 0,0 0,0 0,0
°C/°F
SLH Minimum HACCP alarm signals threshold. -55,0...150 0,0 0,0 0,0 0,0 °C/°F
drA
Minimum time spent in critical range for the event to be recorded. After this a HACCP
alarm will be triggered and logged.
0 ... 99 0 0 0 0 min
drH HACCP alarm reset time after last reset. 0 ... 250 0 0 0 0 hours