PAR. DESCRIPTION RANGE APP1 APP2 APP3 APP4 M.U.
dCt
Selection of count mode for the defrost interval.
0 = compressor running time; 1 = appliance running time;
2 = A defrost cycle is run at each compressor stop
0/1/2 1 1 1 1 num
dOH Delay for start of first defrost after request 0 ... 59 0 0 0 0 min
dEt Defrost timeout; determines the maximum defrost duration 1 ... 250 30 30 30 30 min
dSt Defrost end temperature - determined by probe Pb2 -50,0...150 8,0 8,0 8,0 50,0 °C/°F
dPO Determines whether the instrument must enter defrost mode at start-up n/y n n n n flag
FANS (“FAn” folder)
FSt
Fans stop temperature -58,0...302
50,0 50,0 50,0 50,0 °C/°F
FAd Fan activation differential 1,0 ... 50,0 2,0 2,0 2,0 2,0 °C/°F
Fdt Fan activation delay after a defrost cycle 0 ... 250 0 0 0 0 min
dt Coil drainage time 0 ... 250 0 0 0 0 min
dFd
Allows evaporator fan exclusion to be selected or not selected during defrosting.
y = yes (fans excluded); n = no
n/y y y y y flag
FCO
Selects or deselects fan deactivation at compressor OFF.
0 = fans off; 1 = fans active; 2 = duty cycle
0/1/2 0 0 0 0 num
FOn Fans ON time in day duty cycle 0 ... 99 0 0 0 0 min
FOF Fans OFF time in day duty cycle 0 ... 99 0 0 0 0 min
Fnn Fans ON time in night duty cycle 0 ... 99 0 0 0 0 min
FnF Fans OFF time in night duty cycle 0 ... 99 0 0 0 0 min
ESF Night mode activation. n = no; y = yes n/y n n n n flag
ALARMS (“AL” folder)
Att
Can be used to select absolute (Att=0) or relative (Att=1) values for HAL and LAL
parameters
0/1
0 0 0 0
num
Afd Alarm differential 1,0 ... 50,0 2,0 2,0 2,0 2,0 °C/°F
HAL Maximum temperature alarm LAL...302 50,0 50,0 50,0 50,0 °C/°F
LAL Minimum temperature alarm -58,0...HAL -50,0 -50,0 -50,0 -50,0 °C/°F
PAO Alarm exclusion time after re-activation following a power failure 0 ... 10 0 0 0 0 hours
dAO Temperature alarm exclusion time after defrost 0 ... 999 0 0 0 0 min