Quick Start Guide Flatpack2 PS System, 4U, SP2-based 356825.103, 2v0 -2011-09
19
Correct Rectifier Positions in Power Shelves
Flatpack2 DC power systems are normally shipped from factory with empty power shelves. The
rectifier modules are shipped in separate packaging, and you have to install the modules in the
correct position in the power shelves, with respect to their ID number (or CAN bus address). Do
not relocate already pre-installed rectifiers.
For first time installations of rectifiers in Flatpack2 systems, follow the scheme below:
1. Find out your system’s power shelf type, by
reading the Identifying Power Shelves section, page14
2. Find out if your system’s AC mains feed is
<230VAC, 3 phase> or <400VAC, 3 phase and N>
3. Insert & hot-plug the rectifiers in the indicated power shelf positions,
one module at a time, allowing a 2s delay between them and starting with ID number 1,
2, 3, and so on. (indifferent after ID# 6)
Follow one of the four figures (I, II, III or IV) below:
A
C Mains Appendix
Smartpack2 Master and Smartpack Located in Distribution Shelf
Correct Rectifier Position in 4AC Power Shelves (I)
Single AC feed: 4 AC inputs per shelf, each feeding 1 rectifier
Mains
Three-
p
hase, 230VAC
Mains
Three-
p
hase & N, 400VAC
and
01
02
05
06
---
---
03
04
---
---
---
---
---
---
---
---
Position 1
Position 4
ID number
(Assigned CAN
bus address)
Flatpack
2
rectifie
r
Position 8
Position 9
Smartpac
k
controlle
r
Correct Rectifier Position in 2AC Power Shelves (II)
Dual AC feed: 2 AC inputs per shelf, each feeding 2 rectifiers
Mains
Three-
p
hase, 230VAC
Mains
Three-
p
hase & N, 400VAC
and
01
04
03
06
---
---
02
05
---
---
---
---
---
---
---
---
Position 1
Position 4
Flatpack
2
rectifie
r
Position 8
Position 9
Smartpac
k
controlle
r
ID number
(Assigned CAN
bus address)
Notice:
For Smartpack2-based systems follow
figure I or II, as the Smartpack2 Master
controller is always mounted in the
distribution shelf. The examples in the
figures show Smartpack-based systems.
Phase 1 Phase 2 Phase 3
Smartpack Located in Power Shelf
Correct Rectifier Position in 4AC Power Shelves (III)
Single AC feed: 4 AC inputs per shelf, each feeding 1 rectifier
Mains
Three-
p
hase, 230VAC
Mains
Three-
p
hase & N, 400VAC
and
02
05
06
---
---
03
01
04
---
---
---
---
---
---
---
Position 1
Position 8
Smartpac
k
controlle
r
Position 9
ID number
(Assigned CAN
bus address)
Flatpack
2
rectifie
r
Position 4
Correct Rectifier Position in 2AC Power Shelves (IV)
Dual AC feed: 2 AC inputs per shelf, each feeding 2 rectifiers
Mains
Three-
p
hase, 230VAC
Mains
Three-
p
hase & N, 400VAC
and
01
03
06
---
---
02
05
04
---
---
---
---
---
---
---
ID number
(Assigned CAN
bus address)
Position 1
Position 4
Flatpack
2
rectifie
r
Position 8
Position 9
Smartpac
k
controlle
r

Other manuals for Eltek Valere Flatpack2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eltek Valere Flatpack2 and is the answer not in the manual?

Eltek Valere Flatpack2 Specifications

General IconGeneral
BrandEltek Valere
ModelFlatpack2
CategoryPower Supply
LanguageEnglish

Related product manuals