EasyManua.ls Logo

Eltek FlatpackS 48/1000 HE - 5 Technical Specifications

Default Icon
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Erro! Use a guia Página Inicial para aplicar Heading 1 ao texto que deverá
aparecer aqui. Erro! Use a guia Página Inicial para aplicar Heading 1 ao texto
que deverá aparecer aqui.
User’s Guide FlatpackS Rectifier & Supervision Modules, 17
5. Technical Specifications
Model
48/1000 HE
48/1800 HE
Part number
241122.105
241122.125
INPUT DATA
Voltage (nominal)
185 - 270 V
AC
/ 185 - 250 V
DC
1)
195
2)
- 277 V
AC
/ 195
2)
- 250 V
DC
1)
Voltage (operating range)
85 - 300 V
AC
/ 85 - 250 V
DC
1)
85
2)
- 305 V
AC
/ 85
2)
- 250 V
DC
1)
Current (maximum) @ nominal input, full load
5.9 A
RMS
9.9 A
RMS
Frequency
45 - 66 Hz / 0 Hz
1)
Power Factor
> 0.99 at 50% load or more
Protection
Fuse in L & N
Varistor
Shutdown when input voltage is out of operating range
OUTPUT DATA
Voltage (default)
53.5 V
DC
Voltage (adjustable range)
43.5 - 57.6 V
DC
Power (maximum) @ nominal input
1000 W
1800 W
Power @ 85 VAC
420 W
700 W
2)
Current (maximum) @ nominal input
20.9 A (@V
OUT
< 48V
DC
)
37.5 A (@V
OUT
< 48V
DC
)
Hold up time, maximum output power
>20ms; output voltage > 41 V
DC
>10ms; output voltage > 42 V
DC
Current sharing (10 - 100% load)
±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load)
±0.5%
Dynamic Voltage regulation
±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
Ripple
< 150 mV
PP
, 30 MHz bandwidth
Protection
ORing FET
Short circuit proof
High temperature protection
Over voltage Shutdown
OTHER SPECIFICATIONS
Efficiency
Up to 95.5 %
Up to 95.8 %
Isolation
3.0 kV
AC
- input to output
1.5 kV
AC
- input to earth
710 V
DC
- output to earth
Alarms: Red LED
Low and high input voltage shutdown, High and low temperature shutdown, Rectifier
Failure, Overvoltage shutdown on output, Fan failure, Low output voltage alarm, CAN
bus failure
Warnings: Yellow LED
Rectifier in power de-rate mode, Remote output current limit activated, Input voltage
out of range, flashing at overvoltage, Loss of CAN communication with controller
Normal operation: Green LED
MTBF (Telcordia SR-332 Issue I method III (a))
>315 000 (@ T
ambient
: 25 °C)
>300 000 (@ T
ambient
: 25 °C)
Operating temperature (5-95% RH n.cond.
hum.)
Maximum output power de-rates above temp /
to
-40 to + 85°C [-40 to +185°F]
45°C [113°F] / 600W @ 85°C[185°F]
-40 to + 85°C [-40 to +185°F]
45°C [113°F] / 1000W @ 85°C[185°F]
Storage temperature
-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight
72 x 41.5 x 217mm (2.83 x 1.63 x 8.54”) / < 850 g (1.9 lbs)
DESIGN STANDARDS
Electrical safety
UL 60950-1, EN 60950-1
EMC
ETSI EN 300 386
EN 61000-6-1 / -2 / -3 / -4 TS 61000-6-5
FCC CFR 47 Part 15
Environment
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant