User’s Guide FlatpackS Rectifier & Supervision Modules, 17
5. Technical Specifications
185 - 270 V
AC
/ 185 - 250 V
DC
1)
195
2)
- 277 V
AC
/ 195
2)
- 250 V
DC
1)
Voltage (operating range)
85 - 300 V
AC
/ 85 - 250 V
DC
1)
85
2)
- 305 V
AC
/ 85
2)
- 250 V
DC
1)
Current (maximum) @ nominal input, full load
> 0.99 at 50% load or more
Fuse in L & N
Varistor
Shutdown when input voltage is out of operating range
Voltage (adjustable range)
Power (maximum) @ nominal input
Current (maximum) @ nominal input
Hold up time, maximum output power
>20ms; output voltage > 41 V
DC
>10ms; output voltage > 42 V
DC
Current sharing (10 - 100% load)
±5% of maximum current from 10 to 100% load
Static Voltage regulation (10 - 100% load)
Dynamic Voltage regulation
±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms
< 150 mV
PP
, 30 MHz bandwidth
ORing FET
Short circuit proof
High temperature protection
Over voltage Shutdown
3.0 kV
AC
- input to output
1.5 kV
AC
- input to earth
710 V
DC
- output to earth
Low and high input voltage shutdown, High and low temperature shutdown, Rectifier
Failure, Overvoltage shutdown on output, Fan failure, Low output voltage alarm, CAN
bus failure
Rectifier in power de-rate mode, Remote output current limit activated, Input voltage
out of range, flashing at overvoltage, Loss of CAN communication with controller
Normal operation: Green LED
MTBF (Telcordia SR-332 Issue I method III (a))
>315 000 (@ T
ambient
: 25 °C)
>300 000 (@ T
ambient
: 25 °C)
Operating temperature (5-95% RH n.cond.
hum.)
Maximum output power de-rates above temp /
to
-40 to + 85°C [-40 to +185°F]
45°C [113°F] / 600W @ 85°C[185°F]
-40 to + 85°C [-40 to +185°F]
45°C [113°F] / 1000W @ 85°C[185°F]
-40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] / Weight
72 x 41.5 x 217mm (2.83 x 1.63 x 8.54”) / < 850 g (1.9 lbs)
ETSI EN 300 386
EN 61000-6-1 / -2 / -3 / -4 TS 61000-6-5
FCC CFR 47 Part 15
ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class 3.2)
RoHS (2011/65/EU) and WEEE (2002/96/EC) compliant