Quick Installation Guide
00825-0100-4001, Rev BA
November 2002
Model 3051
E7 SAA Explosion-Proof (Flame-Proof)
Certification No.: AUS EX 1347X
Ex d IIC T6 (T
amb
= 40 °C)
Ex d IIC T5 (T
amb
= 80 °C)
DIP T6 (T
amb
= 40 °C)
DIP T5 (T
amb
= 80 °C)
IP65
Special Conditions for Safe Use (x): It is a condition of safe use for
transmitter enclosures having cable entry thread other than metric
conduit thread that the equipment be utilized with an appropriate
certified thread adaptor.
N7 SAA Type n (Non-sparking)
Certification No.: AUS EX 1249X
Ex n IIC T4 (T
amb
= 70 °C)
Ex n IIC T5 (T
amb
= 40 °C)
IP65
Special Conditions for Safe Use (x): Where the equipment is
installed such that there is an unused conduit entry, it must be
sealed with a suitable blanking plug to maintain the IP40 degree of
protection. Any blanking plug used with the equipment shall be of
a type which requires the use of a tool to effect its removal.
Voltage source shall not exceed 60V ac or 75V dc.
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is
specified. Once a device labeled with multiple approval types is
installed, it should not be reinstalled using any other approval types.
Permanently mark the approval label to distinguish it from unused
approval types.
K5 E5 and I5 combination
KB K5 and C6 combination
K6 C6, I1, and E8 combination
K8 E8 and I1 combination
K7 E7, I7, and N7 combination