02/02
81
Cable A: 5 wires + screen
Aux. Batt. Distribution box. Battery Cabinet or Battery Switch Box
Connector X3 (F) Connector X1 on 100202120009 (screws)
Pin 1 not connected Screen
Pin 2 Pin 5
Pin3 Pin 4
Pin4 Pin 3
Pin 5 Pin 2
Pin6 Pin 1
Cable B: 2 wires + screen
Connector X1 (F) 2
nd
Temperature Sensor in Battery (screws)
Pin 12 screen Pin 3 not connected
Pin 11 Pin 2
Pin 10 Pin 1
Cable C: 5 wires + screen
Connector X3 on UPS cabinet Connector X2 or X3 on Aux. Batt. Dist. Box
Pin 1 not connected Pin 1 screen
Pin 2 Pin 2
Pin 3 Pin 3
Pin 4 Pin 4
Pin 5 Pin 5
Pin 6 Pin 6
Cable D: 3 wires + screen
Cables of removed T11 in UPS cabinet Connector X2 or X3 on Aux. Batt. Dist. Box
Wire 68 Pin 10
Wire 69 Pin 9
Wire 70 Pin 8
Not connected Pin 7 screen