EasyManua.ls Logo

Emerson 7400M Series - 7.5 Specifications for 1+1 Configuration

Emerson 7400M Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
02/02
82
7.4 Specifications for 1+1 Configuration
Specifications are same than single module with the exceptions:
Input Rating Units All models
Permissible input variation Hz
± 2 fixed
Output Paralleled Inverters Ratings Units All Models
Maximum unbalance in current outputs %
± 5% of single module rated current
Maximum load allowable to commutate from bypass
to inverters
% 200% of single module rated current
Maximum load allowable during overload % 300% of single module rated current
Maximum voltage unbalance to maintain parallel
&
±10% of output rated voltage
Maximum velocity variation of output frequency Hz/sec 0.1 fixed
Frequency stability (not synchronized) % 0.1% when input supply frequency is outside the
synchronizing range.
7400M
-
Series UPS User Manual
Single Module and 1+N Parallel System

Table of Contents