11
Note:
• The rating condition is based on a return gas temperature of 5°C.
• Power includes condenser fan.
• Ambient 38°C and 43°C are typical design conditions for unit selection.
Model
Am-
bient
temp
(°C)
Evaporating temperature (°C)
-40 -35 -30 -25 -20 -15 -10 -5 0
Min Nor Max Min Nor Max Min Nor Max Min Nor Max Min Nor Max Min Nor Max Min Nor Max Min Nor Max Min Nor Max
ZXLV
030BE
Capacity (kW)
27
0.79 1.86 2.50 0.94 2.40 3.16 1.21 2.93 3.87 1.45 3.84 5.02 1.75 4.52 5.77 2.17 5.29 6.65 2.62 6.28 7.98 3.10 7.26 9.11 3.65 8.07 9.80
32
0.73 1.82 2.38 0.92 2.30 3.01 1.15 2.86 3.70 1.39 3.69 4.82 1.62 4.28 5.51 2.07 5.13 6.42 2.50 6.01 7.63 2.99 7.00 8.75 3.52 7.78 9.46
38
0.71 1.72 2.27 0.87 2.22 2.89 1.10 2.67 3.61 1.36 3.55 4.63 1.52 4.04 5.15 1.88 4.82 6.17 2.34 5.72 7.25 2.89 6.67 8.37 3.38 7.26 8.82
43
0.66 1.65 2.17 0.84 2.11 2.74 1.06 2.60 3.39 1.29 3.35 4.38 1.40 3.77 4.90 1.80 4.63 5.96 2.21 5.38 6.55 2.76 6.33 7.90 3.16 6.83 8.38
Power (kW)
27
0.84 1.79 2.33 0.85 1.90 2.46 0.86 2.00 2.33 0.86 2.05 2.40 0.89 2.17 2.98 0.87 2.32 3.20 0.87 2.37 3.37 0.90 2.56 3.58 0.91 2.71 3.82
32
0.94 1.99 2.64 0.95 2.05 2.74 0.95 2.19 2.60 0.95 2.29 2.71 0.98 2.39 3.26 0.99 2.56 3.45 1.00 2.61 3.65 1.00 2.83 3.97 1.02 3.01 4.30
38
1.08 2.28 3.10 1.09 2.36 3.18 1.09 2.53 3.00 1.07 2.59 3.07 1.13 2.71 3.64 1.13 2.88 3.89 1.13 2.91 4.13 1.15 3.16 4.43 1.19 3.36 4.77
43
1.22 2.63 3.54 1.23 2.67 3.66 1.25 2.83 3.36 1.25 2.94 3.48 1.25 3.04 4.06 1.27 3.21 4.32 1.30 3.26 4.59 1.30 3.52 4.89 1.32 3.68 5.18
ZXLV
040BE
Capacity (kW)
27
1.00 2.36 3.17 1.19 3.04 4.00 1.53 3.71 4.90 1.83 4.86 6.36 2.22 5.73 7.30 2.75 6.70 8.42 3.32 7.95 10.11 3.93 9.20 11.54 4.62 10.2212.42
32
0.92 2.31 3.02 1.16 2.91 3.81 1.46 3.63 4.69 1.76 4.68 6.11 2.05 5.42 6.98 2.62 6.49 8.13 3.17 7.61 9.67 3.79 8.87 11.09 4.46 9.86 11.98
38
0.90 2.18 2.88 1.10 2.82 3.67 1.39 3.38 4.58 1.72 4.50 5.86 1.93 5.12 6.53 2.38 6.11 7.82 2.96 7.24 9.19 3.66 8.45 10.60 4.28 9.20 11.17
43
0.83 2.09 2.75 1.07 2.67 3.47 1.34 3.30 4.30 1.63 4.24 5.55 1.78 4.77 6.21 2.28 5.86 7.55 2.79 6.82 8.29 3.49 8.02 10.01 4.00 8.65 10.61
Power (kW)
27
1.07 2.34 3.15 1.08 2.48 3.32 1.09 2.62 3.15 1.09 2.67 3.24 1.13 2.84 4.01 1.11 3.03 4.31 1.11 3.09 4.54 1.14 3.35 4.82 1.16 3.54 5.15
32
1.19 2.60 3.56 1.21 2.67 3.70 1.21 2.86 3.51 1.21 2.99 3.65 1.25 3.12 4.39 1.26 3.34 4.65 1.27 3.40 4.92 1.27 3.69 5.35 1.30 3.93 5.80
38
1.37 2.98 4.18 1.39 3.08 4.29 1.38 3.30 4.04 1.36 3.38 4.14 1.44 3.54 4.90 1.44 3.76 5.25 1.44 3.80 5.57 1.46 4.12 5.97 1.51 4.39 6.43
43
1.55 3.44 4.76 1.56 3.49 4.93 1.59 3.69 4.52 1.59 3.84 4.68 1.58 3.97 5.47 1.61 4.19 5.82 1.65 4.26 6.19 1.65 4.59 6.58 1.67 4.81 6.97
Performance data R404A