CSI 9420 publishing policy menuFigure 2-40:
Recommended (default) publishing policy settingsTable 2-11:
Network
size
Interval
(D.HH:MM)
Gateway
credits
Device
credits Notes
N
N/4 days
(but never less
than 14.00:00)
N*8 8
High-resolution data limited
only to 4 devices per day with
most frequent collection interval
of 2 weeks for 1-64 devices.
After 64 devices, the collection
interval increases to (N/4) days.
AMS Machinery Manager v5.61 features an auto-calculate button that populates the CSI
9420 Publishing Policy menu with default values shown in Table 2-11.
If a gateway is dedicated to vibration monitoring and will not be routing any process data,
then you can customize the publishing policy to allow more diagnostic data to be
collected. Follow these steps:
1. Use the settings in Table 2-12 and Table 2-13 to achieve the maximum network size
as indicated.
Configuration
66 MHM-97408, Rev 15