48 Digistart IS User Guide
www.controltechniques.com Issue: 4
Parameter Group
Parameters
Default Value
3 - Digital Inputs
M
3A
Input A Function
Emergency Stop
3B
Input A Name
Emergency Stop
3C
Input A Trip
Always Active
3D
Input A Initial Delay
00:00 (minutes:seconds)
3E
Input A Trip Delay
00:00 (minutes:seconds)
3F
Input B Function
Input Trip (N/O)
3G
Input B Name
Input Trip
3H
Input B Trip
Always Active
3I
Input B Initial Delay
00:00 (minutes:seconds)
3J
Input B Trip Delay
00:00 (minutes:seconds)
3K
Input C Function
Off
3L
Input D Function
Off
3M
Local/Remote
LCL/RMT Anytime
3N
Remote Reset Logic
Normally Closed (N/C)
3O
Comms in Remote
Enable Ctrl in RMT
4 - Digital Outputs
M
4A
Relay A Action
Main Contactor
4B
Relay A On Delay
00:00 (minutes:seconds)
4C
Relay A Off Delay
00:00 (minutes:seconds)
4D
Relay B Action
Run
4E
Relay B On Delay
00:00 (minutes:seconds)
4F
Relay B Off Delay
00:00 (minutes:seconds)
4G
Relay C Action
Trip
4H
Relay C On Delay
00:00 (minutes:seconds)
4I
Relay C Off Delay
00:00 (minutes:seconds)
4J
Relay D Action
Off
4K
Relay E Action
Off
4L
Relay F Action
Off
5 - Protection Settings
M
5A
Excess Start Time
00:20 (minutes:seconds)
5B
Excess Start Time-2
00:20 (minutes:seconds)
5C
Current Imbalance
30%
5D
Phase Sequence
Any Sequence
5E
Underpower
20%
5F
Overpower
400%
5G
Reserved
100 V
5H
Reserved
800 V
5I
Frequency Check
Start/Run
5J
Frequency Variation
±5 Hz
5K
Ground Fault Level
100 mA
5L
Motor Temperature Check
Do Not Check
6 - Protection Delays
M
6A
Current Imbalance Delay
00:03 (minutes:seconds)
6B
Underpower Delay
00:05 (minutes:seconds)
6C
Overpower Delay
00:00 (minutes:seconds)
6D
Reserved
-
6E
Reserved
-
6F
Frequency Delay
00:01 (minutes:seconds)
6G
Restart Delay
00:10 (minutes:seconds)
6H
Ground Fault Delay
00:03 (minutes:seconds)
7 - Set Points
M
7A
Low Current Flag
50%
7B
High Current Flag
100%
7C
Motor Temperature Flag
80%
7D
Mains Reference Voltage
400 V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Digistart IS1x0043B series and is the answer not in the manual?

Emerson Digistart IS1x0043B series Specifications

General IconGeneral
BrandEmerson
ModelDigistart IS1x0043B series
CategoryController
LanguageEnglish

Related product manuals