60 Digistart IS User Guide
www.controltechniques.com Issue: 4
No
Function
Range
Default
8H
Analog Output B
Current (%FLC), Motor Temp (%), Motor kW
(%), Motor kVA (%), Motor pf, Voltage
(%Mains)
Current (%FLC)
8I
Analog B Scale
0-20, 4-20 mA
4-20 mA
8J
Analog B Maximum Adjustment
0 to 600%
100%
8K
Analog B Minimum Adjustment
0%
See Pr 8D to 8G for details of parameter options.
NOTE
Analog Output B is only available if the input/output expansion card is installed.
8.8.10 Group 9 - Display
No
Function
Range
Default
9A
Languages
English, Français, Italiano, Deutsch,
Español, Chinese
Selects which language the keypad will use to display messages and feedback.
No
Function
Range
Default
9B
User Screen - Top Left
Blank, Starter State, Motor Current, Motor
pf, Mains Frequency, Motor kW, Motor HP,
Motor Temp, kWh, Hours Run, Analog Input,
Motor kVA, % Rated kW, Motor Parameter
Set
Motor Current
Selects which information will be displayed on the programmable monitoring screen.
Blank
Displays no data in the selected area, allowing long messages to be shown without
overlapping.
Starter State
The starter's operating state (starting, running, stopping or tripped). Only available for
top left and bottom left positions on the screen.
Motor Current
The average current measured on three phases.
Motor pf
The motor's power factor, measured by the soft starter.
Mains Frequency
The average frequency measured on three phases.
Motor kW
The motor's running power in kilowatts.
Motor HP
The motor's running power in horsepower.
Motor Temp
The motor's temperature, calculated by the thermal model.
kWh
The number of kilowatt hours the motor has run via the soft starter.
Hours Run
The number of hours the motor has run via the soft starter.
Analog Input
The level of analog input A (see Pr 8A to 8C). This setting is only available if the
input/output expansion option is installed.
Motor kVA
The motor's apparent running power in kVA.
% Rated kW
The motor's running power as a percentage of rated kW. Power factor is assumed to
be 1.0 at 100% kW.
Motor Parameter Set
Whether the starter is controlling the motor using the primary motor set (M1) or the
secondary motor set (M2).
No
Function
Range
Default
9C
User Screen - Top Right
Blank, Motor Current, Motor pf, Mains
Frequency, Motor kW, Motor HP, Motor
Temp, kWh, Hours Run, Analog Input, Motor
kVA, % Rated kW
Motor pf
9D
User Screen - Bottom Left
Blank, Starter State, Motor Current, Motor
pf, Mains Frequency, Motor kW, Motor HP,
Motor Temp, kWh, Hours Run, Analog Input,
Motor kVA, % Rated kW
Hours Run
9E
User Screen - Bottom Right
Blank, Motor Current, Motor pf, Mains
Frequency, Motor kW, Motor HP, Motor
Temp, kWh, Hours Run, Analog Input, Motor
kVA, % Rated kW
kWh
No
Function
Range
Default
9F
Graph Data
Current (%FLC), Motor Temp (%), Motor kW
(%), Motor kVA (%), Motor pf
Current (%FLC)
Selects which information the graph will display. See Pr 8D for details of parameter options.