Quick Start
Commissioning
Digistart IS User Guide 61
Issue: 4 www.controltechniques.com
10 seconds, 30 seconds, 1 minute, 5
minutes, 10 minutes, 30 minutes, 1 hour
Sets the graph time scale. The graph will progressively replace the old data with new data.
Adjusts the upper and lower limits of the performance graph.
None, Setup Auto-Start/Stop
Selects the function of the shortcut buttons on the keypad.
If the adjustment lock is on (Pr 15C Adjustment Lock is set to Read Only), users will not be able to change the
auto-start/stop settings.
Calibrates the soft starter's current monitoring circuits to match an external current metering device.
Current shown on Digistart IS display
Current measured by external device
This adjustment affects all current-based functions and protections.
Selects whether the Digistart IS will display current (amperes) or motor kilowatts on the main monitoring screen.
8.8.11 Group 10 - Auto-reset
The Digistart IS can be programmed to automatically reset certain trips, which can help minimise operating downtime. Trips are
divided into three categories for auto-reset, depending on the risk to the soft starter:
Table 8-6 Auto-reset groups
Current Imbalance
Phase loss
Power loss
Frequency
Underpower
Overpower
Input A trip
Input B trip
Motor overload
RTD/PT100 temperature trips
Motor thermistor
Heatsink overtemperature
Other trips cannot be automatically reset.
Do Not Auto-Reset, Reset Group A, Reset
Group A & B, Reset Group A, B & C
Selects which trips can be auto-reset.
Sets how many times the soft starter will auto-reset, if it continues to trip. The reset counter increases by one each time the soft
starter auto-resets, and decreases by one after each successful start/stop cycle.