Emerson Dixell XWi70K - Parameter List (LT Configuration - Part 3); Parameter List (NT Configuration - Part 3)

Emerson Dixell XWi70K
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx XWi70K 13/15
dAF_nt
Pre-defrost time
0
Pr1
min
od1_nt
Automatic defrost (at the beginning of any energy
saving)
no
Pr2
od2_nt
Optimized defrost
no
Pr2
Syd_nt
Tipe of synchronized defrost
nU
Pr2
dt1_nt
Differential temperature for latent heating control
0,2
Pr2
°C
ndE_nt
Number of connected controllers for random refrost
(Syd=rnd)
1
Pr2
FAP_nt
Probe selection for evaporator fan
nP
Pr1
FSt_nt
Evaporator fan stop temperature
20.0
Pr1
°C
HyF_nt
Evaporator fan regulator differential
5.0
Pr1
°C
FnC_nt
Evaporator fan operating mode
C_n
Pr1
Fnd_nt
Evaporator fan delay after defrost cycle
1
Pr1
min
FCt_nt
Differential temperature for cyclic activation of
evaporator fans (0=disabled)
0
Pr1
°C
Fon_nt
Evaporator fan ON time in normal mode (with
compressor OFF)
1
Pr2
min
FoF_nt
Evaporator fan OFF time in normal mode (with
compressor OFF)
1
Pr2
min
LA1_nt
Maintenance interval for evaporator fans (tens of
hours)
0
Pr2
hour *100
rS1_nt
Maintenance function reset
no
Pr2
FAC_nt
Probe selection for condenser fan
nP
Pr2
St2_nt
Set Point 2 Regulation (for condenser fan)
15.0
Pr2
°C
Hy2_nt
Set Point 2 differential (for condenser fan)
20.0
Pr2
°C
FCC_nt
Condenser fan operating mode
C_n
Pr1
FCo_nt
Condenser fan deactivation delay
20
Pr1
sec
LA2_nt
Condenser fan working hours (x100) for
maintenance alarm
0
Pr2
hour *100
rS2_nt
Condenser fan maintenance alarm reset
no
Pr2
CMi_nt
Minimum speed for condenser fan
20
Pr2
%
CMA_nt
Maximum speed for condenser fan
100
Pr2
%
CSS_nt
Safety speed for condenser fan
80
Pr2
%
ACH_nt
Type of control for auxiliary regulator
CL
Pr1
SAA_nt
Set point for auxiliary regulator
0.0
Pr1
°C
SHy_nt
Auxiliary regulator differential
5.0
Pr1
°C
ArP_nt
Probe selection for auxiliary regulator
nP
Pr1
Sdd_nt
Auxiliary regulator disabled during any defrost
cycle
yes
Pr1
btA_nt
Base time for parameters Ato and AtF
Min
Pr1
Ato_nt
Interval of time with auxiliary output ON
0
Pr1
min
AtF_nt
Interval of time with auxiliary output OFF
0
Pr1
min
1An_nt
Type of analogue output 1
Vlt
Pr1
1oL_nt
Minimum value for analogue output 1
5
Pr1
%
1oH_nt
Maximum value for analogue output 1
100
Pr1
%
1At_nt
Interval of time with analogue output 1 (maximum
value)
5
Pr1
sec
2An_nt
Type of analogue output 2
Vlt
Pr1
2oL_nt
Minimum value for analogue output 2
5
Pr1
%
2oH_nt
Maximum value for analogue output 2
100
Pr1
%
2At_nt
Interval of time with analogue output 2 (maximum
value)
5
Pr1
sec
ALP_nt
Probe selection for temperature alarms
nP
Pr1
ALC_nt
Temperature alarms configuration: relative,
absolute
Ab
Pr1
ALU_nt
High temperature alarm
150.0
Pr1
°C
ALL_nt
Low temperature alarm
-100.0
Pr1
°C
AFH_nt
Temperature alarm differential
5.0
Pr2
°C
ALd_nt
Temperature alarm delay
0
Pr1
min
dot_nt
Temperature alarm delay with open door
0
Pr1
min
dAo_nt
Temperature alarm delay at start-up
00:00
Pr1
hour
AP2_nt
Probe selection for 2nd temperature alarm
nP
Pr2
AL2_nt
2nd low temperature alarm
100.0
Pr2
°C
AU2_nt
2nd high temperature alarm
5.0
Pr2
°C
AH2_nt
2nd temperature alarm differential
5.0
Pr2
°C
Ad2_nt
2nd temperature alarm delay
0
Pr2
min
dA2_nt
2nd temperature alarm delay at start-up
00:00
Pr2
hour
dE2_nt
Temperature alarm 2 disabled during every defrost
and dripping phase
nU
Pr2
bLL_nt
Compressor OFF due to 2nd low temperature
alarm
no
Pr2
AC2_nt
Compressor OFF due to 2nd high temperature
alarm
no
Pr2
SAF_nt
Differential for anti-freezing control
3.0
Pr1
°C
tbA_nt
Alarm relay deactivation
yes
Pr1
bUM_nt
Buzzer muting
no
Pr1
oA1_nt
Relay output oA1 configuration
FAn
Pr2
oA2_nt
Relay output oA2 configuration
Cnd
Pr2
oA3_nt
Relay output oA3 configuration
LiG
Pr2
oA4_nt
Relay output oA4 configuration
dEF
Pr2
oA5_nt
Relay output oA5 configuration
ALr
Pr2
1Ao_nt
Analogue output 1 configuration
nU
Pr2
2Ao_nt
Analogue output 2 configuration
nU
Pr2
3Ao_nt
Analogue output 3 configuration
nU
Pr2
AoP_nt
Alarm relay polarity
CL
Pr1
i1P_nt
Digital input 1 polarity
CL
Pr1
i1F_nt
Digital input 1 configuration
EAL
Pr1
did_nt
Digital inputs 1 alarm delay (base time depends on
par. ibt)
0
Pr1
min
i2P_nt
Digital input 2 polarity
CL
Pr1
i2F_nt
Digital input 2 configuration
dor
Pr1
d2d_nt
Digital inputs 2 alarm delay (base time depends on
par. ibt)
0
Pr1
min
nPS_nt
Number of external pressure switch alarms before
stopping the regulation
0
Pr2
odC_nt
Compressor and fan status after door opening
F-C
Pr2
rrd_nt
Regulation restart after door alarm
yes
Pr2
HES_nt
Temperature differential in energy saving
1
Pr1
°C
ESt_nt
Energy saving timeout
0
Pr1
hour