25 TECHNICAL DATA
230Vac 10%, 50/60Hz; 110Vac 10%, 50/60Hz
110VAC: 10VA; 230VAC: 10VA
CH620, V620H, T620x and T820x (x=H or T)
Terminal blocks / Terminal Connections
Plug-in or screw terminal block, wire section between 0,5 and 2,5 mm2
Max tightening force: 0.4 N/m for 5,0mm pitch
Real Time Clock: Data maintenance up to 6 months with lithium battery.
Other parameters: internal EEPROM.
2, non-condensing humidity
Ambient Operating Temperature and Humidity
0T50°C; 20-85 rH% (non-condensing humidity)
-10T50°C; 20-85 rH% (non-condensing humidity)
Shipping and storage temperature
-40T85°C; 20-85 rH% (non-condensing humidity)
NTC: -40T110°C, resolution 0.1°C or 1°C (selectable); PT1000: -100T150°C, resolution 0.1°C or 1°C (selectable);
PTC: -50T150°C, resolution 0.1°C or 1°C (selectable)
±1°C relative to the full scale
4 NTC, PTC or PT1000 (configurable); Up to 2 voltage free contacts
HOT-KEY: MAX voltage allowed is 5 VDC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY.
TTL standard available on 5-pin port (HOT-KEY connector); 2-wire RS485 with termination; 6-wire for VCC; Maximum cable length = 2m
Resistive load 14A, 110/230Vac, 30K cycles
Motor load 2HP (12FLA/72LRA), 230Vac, 30K cycles
Motor load 1HP (16FLA/96LRA), 110Vac, 30K cycles
Motor load 4.9FLA/29.4LRA, 110/230Vac, 30K cycles
14(8)A, 230Vac, 30K cycles
Resistive load 10A, 230 Vac, 30K cycles
14A (NO), 230Vac, 50K cycles
Resistive load 10A, 110/230Vac, 30K cycles
Motor load 1/2HP, 230Vac, 30K cycles
Motor load 4.9FLA/29.4LRA (NO), 110/230Vac, 30K cycles
8(3)A (CO), 230Vac, 100K cycles
Resistive load 4A, 250Vac, 100K cycles
Relay Outputs (optional, on request only)
Resistive load 10A, 110/230Vac, 30K cycles
Motor load 1/2HP, 230Vac, 30K cycles
Motor load 4.9FLA/29.4LRA (NO), 110/230Vac, 30K cycles
8(3)A (CO), 230Vac, 100K cycles
Resistive load 14A, 230Vac, 30K cycles
Resistive load 10A, 230Vac, 50K cycles
Resistive load 10A, 230 Vac, 30K cycles
14A (NO), 230Vac, 50K cycles
12A Plug-in terminal block, 14A other types,4A on insulated relay oA5
0-10Vdc; Min load = 10k ohm
4-20mA; Max load = 500 ohm
A1+: V+ or I+
A1-: GND or I-
0-10Vdc; Min load = 10k ohm
4-20mA; Max load = 500 ohm
A2+: V+ or I+
A2-: GND or I-
Frequency output; Supply max voltage = 5Vdc; Max supply current = 10mA; Duty
cycle = 50%; Range = 0 to 166 Hz; Maximum cable length = 2m
Incorporated control, intended to be used in Class I equipment
R290/R600a: relays tested according to IEC EN60079:0 and IEC EN60079:15
IEC/EN 60730-1; IEC/EN 60730-2-9
UL 60730-1; UL 60730-2-9
CAN/CSA-E60730-1; CAN/CSA-E60730-2-9
Tested according to the requirements of the relevant subclauses of IEC/EN 60335-2-89 in conjunction with IEC/EN 60335-1
(*) Depending on the specific model, some of these I/O could not be present.