1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx XWi70K 7/15
DIGITAL INPUT MENU - inP
i1P
Digital input 1 polarity: (oP; CL) oP = activated by closing the contact; CL = activated
by opening the contact.
i1F
Digital input 1 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF;
LiG; CC; EMt)
EAL = external warning alarm
bAL = external lock alarm
PAL = external pressure alarm
dor = door switch function
dEF = defrost activation
AUS = auxiliary output
ES = energy saving mode activation
HdF = holiday defrost
LiG = light output control
onF = ON/OFF status change
Lnt = change configuration (between Lt and nt)
did
Digital input 1 alarm delay: (0 to 255 min) delay between the detection of an external
event and the activation of the relative function.
i2P
Digital input 2 polarity: (oP; CL) oP = activated by closing the contact; CL = activated
by opening the contact.
i2F
Digital input 2 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF;
LiG; CC; EMt)
EAL = external warning alarm
bAL = external lock alarm
PAL = external pressure alarm
dor = door switch function
dEF = defrost activation
AUS = auxiliary output
ES = energy saving mode activation
HdF = holiday defrost
LiG = light output control
onF = ON/OFF status change
Lnt = change configuration (between Lt and nt)
d2d
Digital input 2 alarm delay: (0 to 255 min) delay between the detection of an external
event and the activation of the relative function.
nPS
Number of external pressure switch alarms before stopping the regulation: (0 to
15) after reaching nPS events in the digital input alarm delay (par. dxd), the regulation
will be stopped and a manual restart (ON/OFF, power OFF and power ON) will be
required
odC
Compressor and fan status after door opening: (no; FAn; CPr; F-C): no = normal;
FAn = Fans OFF; CPr = Compressor OFF; F-C = Compressor and fans OFF.
rrd
Regulation restart after door alarm: (n; Y) n = regulation disabled until door open
alarm is ON; Y = when the delay rrd elapses, the regulation restarts even if a door open
alarm is ON.
ENERGY SAVING MENU ES
HES
Temperature differential in energy saving: (-30.0 to 30.0°C; -54 to 54°F) sets the
increasing value of the set point during the Energy Saving cycle.
ESt
Energy saving timeout: (0 to 255 hours) maximum duration for energy saving mode. If
ESt=0 then this function is disabled.
LdE
Energy saving controls the lights: (n; Y) lights off when energy saving mode is active
LHt
Time-out for light output: (0 to 255 min) the light output will be forced OFF after this
period. LHt=0 means function disabled.
REAL TIME CLOCK MENU - rtC
Hur
Hours: 0 to 23 hours
Min
Minutes: 0 to 59 minutes
dAY
Day of the week: Sun to Sat
dYM
Day of the month: 1 to 31
Mon
Month: 1 to 12
YAr
Year: 00 to 99
Hd1
First day of weekend: (Sun to SAt; nu) setting for the first day of the weekend.
Hd2
Second day of weekend: (Sun to SAt; nu) setting for the second day of the
weekend.
iLE
Energy saving cycle starting time on working days: (00h00min to 23h50min)
during the Energy Saving cycle, the set point is increased by the value in HES so
that the operation set point is SET+HES.
dLE
Energy saving cycle duration on working days: (00h00min to 24h00min) sets
the duration of the Energy Saving cycle on working days.
iSE
Energy saving cycle starting time on weekends: 00h00min to 23h50min
dSE
Energy saving cycle duration on weekends: 00h00min to 24h00min
dd1…dd6
Daily defrost enabled: (n; Y) to enable the Ld1 to Ld6 defrost operations for any
day of the week.
dd1 = Sunday defrost
dd2 = Monday defrost
dd3 = Tuesday defrost
dd4 = Wednesday defrost
dd5 = Thursday defrost
dd6 = Friday defrost
dd7 = Sunday defrost
Ld1Ld6
Defrost starting time: (00h00min to 23h50min) these parameters set the
beginning of the programmable defrost cycles during any ddx day. Example: when
Ld2=12.4, the second defrost starts at 12:40 am during working days.
N.B.: To disable a defrost cycle set it to “nu”(not used). Ex: if Ld6=nu; the sixth defrost cycle will
be disabled.
SERIAL COMMUNICATION - CoM
Adr
Serial address: (1 to 247) device address for Modbus communication
bAU
Baudrate: (9.6; 19.2) select the correct baudrate for serial communication
USER INTERFACE - Ui
brd
Type of keyboard lock: (UnL; SEL; ALL)
UnL = function disabled
SEL = only some buttons are locked after tLC
ALL = all buttons are locked after tLC
tLC
Delay before keyboard lock: (0 to 255 sec) this delay is used after power-on to lock
some functions of the keyboard.
onC
ONOFF button configuration: (nU; oFF; ES; SEr)
nU = not used
oFF = to switch on and off the device
ES = energy saving mode
on2
ONOFF button timed configuration (3 sec): (nU; oFF; ES)
nU = disabled
oFF = to switch on and off the device
ES = energy saving mode
LGC
Light button configuration: (nU; oFF; ES; SEr)
nU = not used
LiG = to switch on and off the light output
AUS = acts on the auxiliary output
LG2
Light button timed configuration (3 sec): (nU; oFF; ES)
nU = not used
LiG = to switch on and off the light output
AUS = acts on the auxiliary output
Lnt = to swap the parameter map between “Lt” and “nt”
CC = to load the default factory settings
dFC
Defrost button configuration: (nU; oFF; ES; SEr)
nU = not used
Pb2 = to quickly visualize the current values of probe P2
AUS = acts on the auxiliary output
dF2
Defrost button timed configuration (3 sec): (nU; oFF; ES)
nU = disabled
dEF = to start a defrost
AUS = acts on the auxiliary output
dn2
Down button timed configuration (3 sec): (nU; Std; Lnt; ALr; Pnd)
nU = not used
Std = lower temperature value
Lnt = configuration map change
Pdn = force Pull Down mode
UP2
UP button timed configuration (3 sec): (nU; Std; CC; ALr; Pnd)
nU = not used
Std = higher temperature value
CC = to load the default factory settings
Pnd = force Pull Down mode
Info Menu - Info
dP1
Probe P1 value visualization
dP2
Probe P2 value visualization
dP3
Probe P3 value visualization
dP4
Probe P4 value visualization
SPd
Instantaneous compressor speed (RPM * 10)
rSE
Real regulation Set Point
rEL
Firmware release: progressive number
Ptb
Parameter map version
16 DIGITAL INPUT
The free voltage digital inputs are programmable in different configurations by the i1F or i2F
parameters.
16.1 DOOR SWITCH INPUT (dor)
It signals the door status and the corresponding relay output status through the odC parameter: no =
normal (any change); FAn = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, the
display shows the message “dA” and the regulation restarts is rtr = yES. The alarm stops as soon as
the external digital input is disabled again. With the door open, the high and low temperature alarms are
disabled.
16.2 GENERIC ALARM (EAL)
As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-
activated.
16.3 SERIOUS ALARM MODE (bAL)
When the digital input is activated, the unit will wait for did delay before signalling the CA alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
16.4 PRESSURE SWITCH (PAL)
If during the interval time set by did parameter, the pressure switch has reached the number of activation
of the nPS parameter, the CApressure alarm message will be displayed. The compressor and the
regulation are stopped. When the digital input is ON the compressor is always OFF. If the nPS
activation in the did time is reached, switch off and on the instrument to restart normal
regulation.
16.5 AUXILIARY OUTPUT CONTROL (AUS)
To activate and deactivate the auxiliary output