DIGITAL INPUT MENU - inP
Digital input 1 polarity: (oP; CL) oP = activated by closing the contact; CL = activated
by opening the contact.
Digital input 1 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF;
LiG; CC; EMt)
• EAL = external warning alarm
• bAL = external lock alarm
• PAL = external pressure alarm
• dor = door switch function
• dEF = defrost activation
• AUS = auxiliary output
• ES = energy saving mode activation
• HdF = holiday defrost
• LiG = light output control
• onF = ON/OFF status change
• Lnt = change configuration (between Lt and nt)
Digital input 1 alarm delay: (0 to 255 min) delay between the detection of an external
event and the activation of the relative function.
Digital input 2 polarity: (oP; CL) oP = activated by closing the contact; CL = activated
by opening the contact.
Digital input 2 configuration: (nu; dor; dEF; AUS; ES; EAL; bAL; PAL; FAn; HdF; onF;
LiG; CC; EMt)
• EAL = external warning alarm
• bAL = external lock alarm
• PAL = external pressure alarm
• dor = door switch function
• dEF = defrost activation
• AUS = auxiliary output
• ES = energy saving mode activation
• HdF = holiday defrost
• LiG = light output control
• onF = ON/OFF status change
• Lnt = change configuration (between Lt and nt)
Digital input 2 alarm delay: (0 to 255 min) delay between the detection of an external
event and the activation of the relative function.
Number of external pressure switch alarms before stopping the regulation: (0 to
15) after reaching nPS events in the digital input alarm delay (par. dxd), the regulation
will be stopped and a manual restart (ON/OFF, power OFF and power ON) will be
required
Compressor and fan status after door opening: (no; FAn; CPr; F-C): no = normal;
FAn = Fans OFF; CPr = Compressor OFF; F-C = Compressor and fans OFF.
Regulation restart after door alarm: (n; Y) n = regulation disabled until door open
alarm is ON; Y = when the delay rrd elapses, the regulation restarts even if a door open
alarm is ON.
Temperature differential in energy saving: (-30.0 to 30.0°C; -54 to 54°F) sets the
increasing value of the set point during the Energy Saving cycle.
Energy saving timeout: (0 to 255 hours) maximum duration for energy saving mode. If
ESt=0 then this function is disabled.
Energy saving controls the lights: (n; Y) lights off when energy saving mode is active
Time-out for light output: (0 to 255 min) the light output will be forced OFF after this
period. LHt=0 means function disabled.
REAL TIME CLOCK MENU - rtC
Day of the week: Sun to Sat
Day of the month: 1 to 31
First day of weekend: (Sun to SAt; nu) setting for the first day of the weekend.
Second day of weekend: (Sun to SAt; nu) setting for the second day of the
weekend.
Energy saving cycle starting time on working days: (00h00min to 23h50min)
during the Energy Saving cycle, the set point is increased by the value in HES so
that the operation set point is SET+HES.
Energy saving cycle duration on working days: (00h00min to 24h00min) sets
the duration of the Energy Saving cycle on working days.
Energy saving cycle starting time on weekends: 00h00min to 23h50min
Energy saving cycle duration on weekends: 00h00min to 24h00min
Daily defrost enabled: (n; Y) to enable the Ld1 to Ld6 defrost operations for any
day of the week.
• dd1 = Sunday defrost
• dd2 = Monday defrost
• dd3 = Tuesday defrost
• dd4 = Wednesday defrost
• dd5 = Thursday defrost
• dd6 = Friday defrost
• dd7 = Sunday defrost
Defrost starting time: (00h00min to 23h50min) these parameters set the
beginning of the programmable defrost cycles during any ddx day. Example: when
Ld2=12.4, the second defrost starts at 12:40 am during working days.
N.B.: To disable a defrost cycle set it to “nu”(not used). Ex: if Ld6=nu; the sixth defrost cycle will
be disabled.
SERIAL COMMUNICATION - CoM
Serial address: (1 to 247) device address for Modbus communication
Baudrate: (9.6; 19.2) select the correct baudrate for serial communication
Type of keyboard lock: (UnL; SEL; ALL)
• UnL = function disabled
• SEL = only some buttons are locked after tLC
• ALL = all buttons are locked after tLC
Delay before keyboard lock: (0 to 255 sec) this delay is used after power-on to lock
some functions of the keyboard.
ONOFF button configuration: (nU; oFF; ES; SEr)
• nU = not used
• oFF = to switch on and off the device
• ES = energy saving mode
ONOFF button timed configuration (3 sec): (nU; oFF; ES)
• nU = disabled
• oFF = to switch on and off the device
• ES = energy saving mode
Light button configuration: (nU; oFF; ES; SEr)
• nU = not used
• LiG = to switch on and off the light output
• AUS = acts on the auxiliary output
Light button timed configuration (3 sec): (nU; oFF; ES)
• nU = not used
• LiG = to switch on and off the light output
• AUS = acts on the auxiliary output
• Lnt = to swap the parameter map between “Lt” and “nt”
• CC = to load the default factory settings
Defrost button configuration: (nU; oFF; ES; SEr)
• nU = not used
• Pb2 = to quickly visualize the current values of probe P2
• AUS = acts on the auxiliary output
Defrost button timed configuration (3 sec): (nU; oFF; ES)
• nU = disabled
• dEF = to start a defrost
• AUS = acts on the auxiliary output
Down button timed configuration (3 sec): (nU; Std; Lnt; ALr; Pnd)
• nU = not used
• Std = lower temperature value
• Lnt = configuration map change
• Pdn = force Pull Down mode
UP button timed configuration (3 sec): (nU; Std; CC; ALr; Pnd)
• nU = not used
• Std = higher temperature value
• CC = to load the default factory settings
• Pnd = force Pull Down mode
Probe P1 value visualization
Probe P2 value visualization
Probe P3 value visualization
Probe P4 value visualization
Instantaneous compressor speed (RPM * 10)
Real regulation Set Point
Firmware release: progressive number
16 DIGITAL INPUT
The free voltage digital inputs are programmable in different configurations by the i1F or i2F
parameters.
16.1 DOOR SWITCH INPUT (dor)
It signals the door status and the corresponding relay output status through the odC parameter: no =
normal (any change); FAn = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, the
display shows the message “dA” and the regulation restarts is rtr = yES. The alarm stops as soon as
the external digital input is disabled again. With the door open, the high and low temperature alarms are
disabled.
16.2 GENERIC ALARM (EAL)
As soon as the digital input is activated the unit will wait for did time delay before signalling the “EAL”
alarm message. The outputs status doesn’t change. The alarm stops just after the digital input is de-
activated.
16.3 SERIOUS ALARM MODE (bAL)
When the digital input is activated, the unit will wait for did delay before signalling the “CA” alarm
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated.
16.4 PRESSURE SWITCH (PAL)
If during the interval time set by did parameter, the pressure switch has reached the number of activation
of the nPS parameter, the “CA” pressure alarm message will be displayed. The compressor and the
regulation are stopped. When the digital input is ON the compressor is always OFF. If the nPS
activation in the did time is reached, switch off and on the instrument to restart normal
regulation.
16.5 AUXILIARY OUTPUT CONTROL (AUS)
To activate and deactivate the auxiliary output