1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx XWi70K 8/15
16.6 DEFROST CONTROL (dEF)
It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will
restart only if the digital input is disabled otherwise the instrument will wait until the MdF safety time is
expired.
16.7 ENERGY SAVING (ES)
The Energy Saving function allows to change the set point value as the result of the SET+HES
(parameter) sum. This function is enabled until the digital input is activated.
16.8 HOLIDAY MODE (HdF)
Holiday mode activation.
16.9 REMOTE LIGHT CONTROL (LIG)
To manage the light activation from remote.
16.10 REMOTE ON OFF (onF)
To issue a remote ON/OFF command.
16.11 PARAMETER MAP CHANGE (Lnt)
To change the used parameter map from nt (first configuration or “normal temperature”) to Lt (second
configuration or “low temperature”) and vice-versa.
16.12 DIGITAL INPUTS POLARITY
The digital input polarity depends on the i1P or i2P parameters:
i1P or i2P=CL: the input is activated by closing the contact.
i1P or i2P=OP: the input is activated by opening the contact
17 HOW TO INSTALL AND MOUNT
The controller XWi70K shall be mounted in a din rail and in a horizontal position or with the relay output
on the bottom side (IEC/60730).
It must be connected to the keyboard by using a 2-wire cable ( 1mm). The temperature range allowed
for correct operation is 0 to 60°C. Avoid places subject to strong vibrations, corrosive gases, excessive
dirt or humidity. The same recommendations apply to probes. Let the air free to circulate by the aeration
holes.
17.1 XWi70K – 8 DIN CASE - DIMENSIONS
18 ELECTRICAL CONNECTIONS
XWi70K is provided with screw terminal blocks to connect cables with a cross section up to 2.5 mm
2
for
the RS485 (optional) and the keyboard. To connect the other inputs, power supply and relays, XWi70K
is provided with Plug-in connections (6.3mm). Heat-resistant cables must be used. Before connecting
cables make sure the power supply complies with the instrument’s requirements. Separate the probe
cables from the power supply cables, from the outputs and the power connections. Do not exceed the
maximum current allowed, in case of heavier loads use a suitable external relay.
NOTE:
- The maximum current allowed for the common line of the relays is 14A (IEC/60730)
- The maximum current allowed for insulated relay (oA5) is 3A (IEC/60730)
18.1 PROBE CONNECTIONS
The probes shall be mounted with the bulb upwards to prevent damages due to liquid infiltration. It is
recommended to place the thermostat probe away from air streams to correctly measure the average
room temperature. Place the defrost termination probe among the evaporator fins in the coldest place,
where most ice is formed, far from heaters or from the warmest place during defrost, to prevent
premature defrost termination.
19 TTL/RS485 SERIAL LINE
The TTL connector allows, by means of the external module TTL/RS485 (XJ485CX), to connect the unit
to a network line ModBUS-RTU compatible as the Dixell monitoring system. The same TTL connector
is used to upload and download the parameter list of the “HOT-KEY”.
20 HOW TO USE OF THE “HOT KEY”
NOTE: the XWi controllers need a 64KB HOT KEY (Dixell code: DK00000300). Standard Hot Key is not
supported.
20.1 PROGRAM A HOT-KEY FROM AN INSTRUMENT (UPLOAD)
1. Program one controller with the front keypad.
2. When the controller is ON, insert the “HOT-KEY” and push UP button; the “uPL” message
appears followed a by a flashing “End” label.
3. Push SET button and the “End” will stop flashing.
4. Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again.
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation.
20.2 HOT TO CHANGE PARAMETER MAP BY USING AN HOT-KEY
(DOWNLOAD)
1. Turn OFF the instrument.
2. Insert a pre-programmed “HOT-KEY” into the 5-PIN port and then turn the Controller ON.
3. The parameter list of the “HOT-KEY” will be automatically downloaded into the Controller
memory. The “doL” message will blink followed a by a flashing “End” label.
4. After 10 seconds the instrument will restart working with the new parameters.
5. Remove the “HOT-KEY”.
NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then on
if you want to restart the download again or remove the “HOT-KEY” to abort the operation.
21 INTERNAL MEMORY
The controller has an internal memory where are stored:
- Parameter maps nt and Lt
- Factory default configurations for both nt and Lt parameters map
The controller is always shipped with:
- Parameter map nt = factory default configuration “nt”
- Parameter map Lt = factory default configuration “Lt”
Any modification to parameter map nt or Lt does not change factory values.
It will be possible to restore factory defaults values for nt or Lt parameters map by using UP2=CC
function.
NOTES:
- If controller is using nt parameter map, the factory default configuration nt will be reloaded
overwriting nt parameter map. The same for parameter map Lt.
- The factory default configurations are read only (it is not possible to modify them on the field).
22 ALARM SIGNALS