EasyManua.ls Logo

Emerson Dixell XWi70K - Defrost Control Functions; Energy Saving Function; Holiday Mode Activation; Remote Light Control

Emerson Dixell XWi70K
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx XWi70K 6/15
FSt
Evaporator fan stop temperature: (-55 to 50°C; -67 to 122°F) setting of temperature,
detected by evaporator probe. Above this temperature value fans are always OFF.
NOTE: it works only for the evaporator fan, NOT for the condenser fan.
HYF
Evaporator fan regulator differential: (0.1 to 25.5°C; 1 to 45°F) evaporator fan will
stop when the measured temperature (from FAP) is T<FSt-HYF.
FnC
Evaporator fan operating mode: (Cn; on; CY; oY)
Cn = runs with the compressor, duty-cycle when compressor is OFF (see FoF,
Fon, FF1 and Fo1 parameters) and OFF during defrost
on = continuous mode, OFF during defrost
CY = runs with the compressor, duty-cycle when compressor is OFF (see FoF,
Fon, FF1 and Fo1 parameters) and ON during defrost
oY = continuous mode, ON during defrost
Fnd
Evaporator fan delay after defrost cycle: (0 to 255 min) delay before fan activation
after any defrosts.
FCt
Differential temperature for cyclic activation of evaporator fans: (0 to 50°C; 0 to
90°F)
Ft
Evaporator fan controlled during defrost: (n; Y)
Fon
Evaporator fan ON time in normal mode (with compressor OFF): (0 to 15 min) used
when energy saving status is not active.
FoF
Evaporator fan OFF time in normal mode (with compressor OFF): (0 to 15 min)
used when energy saving status is not active.
LA1
Evaporator fan working hours (x100) for maintenance alarm: (0 to 999) set the
warning interval for maintenance. NOTE: internal value is multiplied by 100.
rS1
Evaporator fan maintenance function reset: (n; Y) change to Y and confirm with SET
button to reset condenser fan maintenance warning. LA1 interval will be reloaded.
FAC
Probe selection for condenser fan: (nP; P1; P2; P3; P4) nP=no probe; Px=probe “x”.
St2
Set Point 2 regulation (for condenser fan): (-55 to 50°C; -67 to 122°F) setting of
temperature detected by evaporator probe. Above this value of temperature fans are
always OFF.
HY2
Set Point 2 differential (for condenser fan): (0.1 to 25.5°C; 1 to 45°F) differential for
evaporator ventilator regulator
FCC
Condenser fan operating mode: (Cn; on; CY; oY)
Cn = runs with the compressor and OFF during defrost
on = continuous mode, OFF during defrost
CY = runs with the compressor and ON during defrost
oY = continuous mode, ON during defrost
FCo
Condenser fan deactivation delay: (0 to 999 sec) interval with condenser fan on after
stopping compressor and when FCC=C-n or C-Y
LA2
Condenser fan working hours (x100) for maintenance alarm: (0 to 999) set the
warning interval for maintenance. NOTE: internal value is multiplied by 100.
rS2
Condenser fan maintenance alarm reset: change to Y and confirm with SET button
to reset condenser fan maintenance warning. LA2 interval will be reloaded.
AUXILIARY MENU AUS
ACH
Type of control for auxiliary regulator: (CL; Ht) CL = cooling; Ht = heating.
SAA
Set Point for auxiliary regulator: (-100.0 to 150.0°C; -148 to 302°F) it defines the room
temperature set point to switch auxiliary relay.
SHY
Auxiliary regulator differential: (0.1 to 25.5°C; 1 to 45°F) differential for auxiliary
output set point.
ACH=CL, AUX Cut in is [SAA+SHY]; AUX Cut out is SAA.
ACH=Ht, AUX Cut in is [SAASHY]; AUX Cut out is SAA.
ArP
Probe selection for auxiliary regulator: (nP; P1; P2; P3; P4) nP = no probe, the
auxiliary relay is switched only by the digital input; Px=probe “x”. Note: P4=Probe on Hot
Key plug.
Sdd
Auxiliary regulator disabled during any defrost cycle: (n; Y) n = the auxiliary relay
operates during defrost. Y = the auxiliary relay is switched off during defrost.
btA
Base time for parameters Ato and AtF: (SEC; Min) SEC = base time is in seconds;
Min = base time is in minutes.
Ato
Interval of time with auxiliary output ON: (0 to 255) valid if oAx=tiM, x=0,1,2,3,4 or if
xAo=tiM, x=1, 2
AtF
Interval of time with auxiliary output OFF: (0 to 255) valid if oAx=tiM, x=0,1,2,3,4 or
if xAo=tiM, x=1, 2
1An
Type of analogue output 1: (VLt; Cur) VLt = 0-10Vdc; Cur = 4-20mA
1oL
Minimum value for analogue output 1: (0 to 100%) output value at the beginning of
the scale
1oH
Maximum value for analogue output 1: (0 to 100%) output value at the end of the
scale
1At
Interval of time with analogue output 1 (maximum value): (0 to 255 sec) analogue
output is forced at 100%, after any activation, for 1At seconds.
2An
Type of analogue output 2: (VLt; Cur) VLt = 0-10Vdc; Cur = 4-20mA
2oL
Minimum value for analogue output 2: (0 to 100%) output value at the beginning of
the scale
2oH
Maximum value for analogue output 2: (0 to 100%) output value at the end of the
scale
2At
Interval of time with analogue output 2 (maximum value): (0 to 255 sec) analogue
output is forced at 100%, after any activation, for 2At seconds.
ALARM MENU - ALr
ALP
Probe selection for temperature alarms: (nP; P1; P2; P3; P4) nP=no probe; Px=probe
“x”. Note: P4=Probe on Hot Key plug.
ALC
Temperature alarm configuration: (Ab, rE) Ab = absolute; rE = relative.
ALU
High temperature alarm: when this temperature is reached, the alarm is enabled after
the Ad delay time.
If ALC=Ab ALL to 150.0°C or ALL to 302°F.
If ALC=rE 0.0 to 50.0°C or 0 to 90°F.
ALL
Low temperature alarm: when this temperature is reached, the alarm is enabled after
the Ad delay time.
If ALC=Ab -100.0°C to ALU or -148°F to ALU.
If ALC=rE 0.0 to 50.0°C or 0 to 90°F.
AFH
Temperature alarm differential: (0.1 to 25.0°C; 1 to 45°F) alarm differential.
ALd
Temperature alarm delay: (0 to 255 min) delay time between the detection of an alarm
condition and the relative alarm signalling.
dot
Temperature alarm delay with door open: (0 to 255 min) delay between the detection
of a temperature alarm condition and the relative alarm signaling, after starting up the
instrument.
dAo
Temperature alarm delay at start-up: (0.0 to 24h00min, res. 10 min) delay time
between the detection of a temperature alarm condition and the relative alarm signalling,
after starting up the instrument.
dot
Temperature alarm delay with open door: (0 to 255 min)
AP2
Probe selection for second temperature alarm: (nP; P1; P2; P3; P4) nP=no probe;
Px=probe “x”. Note: P4=Probe on Hot Key plug.
AL2
Second low temperature alarm: (-100.0 to 150.0°C; -148 to 302°F)
Au2
Second high temperature alarm: (-100.0 to 150.0°C; -148 to 302°F)
AH2
Second temperature alarm differential: (0.1 to 25.0°C; 1 to 45°F)
Ad2
Second temperature alarm delay: (0 to 254 min; 255 = not used) delay time between
the detection of a condenser alarm condition and the relative alarm signalling.
dA2
Second temperature alarm delay at start-up: (0.0 to 24h00min, res. 10 min)
dE2
Temperature alarm 2 disabled during every defrost and dripping phase: (n; Y)
bLL
Compressor OFF due to second low temperature alarm: (n; Y) n = the compressor
keep on working; Y = the compressor is switched off while the alarm is ON; in any
case, the regulation restarts if delay AC is elapsed.
AC2
Compressor OFF due to second high temperature alarm: (n; Y) n = the
compressor keep on working; Y = the compressor is switched off while the alarm is
ON; in any case, the regulation restarts if delay AC is elapsed.
SAF
Differential for anti-freezing control: (0.0to 25.5°C; 0 to 45°F) the regulation stops if
T<SET-SAF. NOTE: 0 = function disabled.
tbA
Alarm relay deactivation: (n; Y) n = no, it is not possible to deactivate neither the
buzzer nor any digital output set as an alarm; Y = yes, it is possible to deactivate both
the buzzer and the digital output set as an alarm.
bUM
Buzzer muting: (n; Y) n = disabling buzzer deactivation; Y = enabling buzzer
deactivation.
OUTPUT CONFIGURATIONS oUt
oA1
to
oA4
Relay output oAx configuration: (nu; onF; dEF; Fan; Alr; LiG; AuS; db; CP1; CP2;
dF2; HES; Het; inV; tiM; Cnd)
nu = not used
onF = always on with instrument on
dEF = defrost
FAn = evaporator Fan
ALr = alarm
LiG = light
AuS = auxiliary output
db = neutral zone
CP1 = ONOFF compressor
CP2 = second ONOFF compressor
dF2 = second defrost
HES = energy saving
HEt = heater output control
inV = inverter output, relay activated only when inverter is running
(compressor speed > 0)
tiM = timed mode activation
Cnd = condenser fan.
oA5
Relay output oA5 configuration: (nu; onF; dEF; FAn; ALr; LiG; AuS; dF2;
HES; tiM; Cnd;)
nu = not used
onF = always on with instrument on
dEF = defrost
FAn = evaporator Fan
ALr = alarm
LiG = light
AuS = auxiliary output
dF2 = second defrost
HES = energy saving
tiM = timed mode activation
Cnd = condenser fan.
1Ao
Analogue output 1 configuration (4-20mA; 0-10Vdc): (nu, tiM, FAn, AUS, ALr,
Cnd)
nu = not used
tiM = timed mode
FAn = linked to the evaporator fan regulator
AUS = linked to the auxiliary regulator
ALr = linked to any alarm condition
Cnd = linked to the condenser fan regulator
2Ao
Analogue output 2 configuration: (4-20mA; 0-10Vdc): (nu, tiM, FAn, AUS, ALr,
Cnd)
nu = not used
tiM = timed mode
FAn = linked to the evaporator fan regulator
AUS = linked to the auxiliary regulator
ALr = linked to any alarm condition
Cnd = linked to the condenser fan regulator
NOTE: always set 3Ao=nu before using 2Ao analogue output
3Ao
Analogue output 3 configuration: (nu; FrE; ALr)
nu = not used
FrE = frequency output for variable speed compressors
NOTE: when 3Ao is set, 2Ao is automatically deactivated
AoP
Alarm relay polarity: (oP; CL) oP = alarm activated by closing the contact; CL =
alarm activated by opening the contact

Related product manuals