EasyManua.ls Logo

Emerson Dixell XWi70K - Parameter List Overview

Emerson Dixell XWi70K
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592026601 XWi70K STD FULL EN r1.6 2022.07.29.docx XWi70K 5/15
LS
Minimum Set Point: (-100.0°C to SET; -148°F to SET) fix the minimum value for the
set point.
US
Maximum Set Point: (SET to 150.0°C; SET to 302°F) fix the maximum value for the
set point.
HY
Compressor regulation differential in normal mode: (0.1 to 25.0°C; 1 to 45°F) set
point differential. Compressor Cut-IN is T > SET + HY. Compressor Cut-OUT is
T<=SET.
HY1
Proportional band in normal mode: (0.1 to 25.5°C; 1 to 45°F) define a second
regulation band which is used when double ONOFF compressor regulation or a
variable speed compressor is configured.
odS
Output activation delay at start-up: (0 to 255 min) this function is enabled after the
instrument power-on and delays the output activations.
AC
Anti-short cycle delay: (0 to 999 sec) minimum interval between a compressor stop
and the following restart.
AC1
Anti-short cycle delay (2nd compressor): (0 to 999 sec) delay before activating
second compressor, depending on regulation mode selected by par. 2CC
2CC
Activation mode for 2nd compressor (valid if oAx=CP1 and oAy=CP2): (FUL;
HAF) FUL=second compressor will be activated after AC1 delay. HAF=second
compressor will be activated with step logic.
rCC
Enable compressor rotation: (n;Y) n = CP1 is always the first compressor activated.
Y = CP1 and CP2 activation is alternated
MCo
Maximum time with compressor ON: (0 to 255min) maximum time with ONOFF
compressor active. With MCo=0 this function is disabled.
rtr
Regulation percentage=F(P1; P2) (100=P1; 0=P2): 100=P1 only; 0=P2 only
CCt
Maximum duration for Pull Down: (0.0 to 99h50min, res. 10min) after elapsing this
time interval, the super cooling function is immediately stopped.
CCS
Pull Down phase differential (SET+CCS or SET+HES+CCS):
(-12.0 to 12.0°C; -21 to 21°F) during any super cooling phase the regulation
SETPOINT is moved to SET+CCS (in normal mode) or to SET+HES+CCS (in
energy saving mode)
oHt
Threshold for automatic activation of Pull Down in normal mode
(SET+HY+oHt): (0.0 to 25.5°C; 0 to 45°F) this is the upper limit used to activate the
super cooling function.
Con
Compressor ON time with faulty probe: (0 to 255 min) time during which the
compressor is active in case of faulty thermostat probe. With Con=0 compressor is
always OFF.
CoF
Compressor OFF time with faulty probe: (0 to 255 min) time during which the
compressor is OFF in case of faulty thermostat probe. With CoF=0 compressor is
always active.
PROBE MENU Prb
PbC
Probe selection: (ntC; Pt1) ntC=NTC type; Pt1=PT1000 type
ot
Probe P1 calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible
offset of the first probe.
P2P
Probe P2 presence: n = not present; Y = present.
oE
Probe P2 calibration: -12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible
offset of the second probe.
P3P
Probe P3 presence: n = not present; Y = the defrost is present.
o3
Probe P3 calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible
offset of the third probe.
P4P
Probe P4 presence: n = not present; Y = present.
o4
Probe P4 calibration: (-12.0 to 12.0°C; -21 to 21°F) allows to adjust any possible
offset of the fourth probe.
VARIABLE SPEED DRIVE MENU vSC
FMi
Minimum value for Variable Speed Compressor (RPM * 10): (0 to FMA) select
according to the VSC in use
FMA
Maximum value for Variable Speed Compressor (RPM * 10): (FMi to 500) select
according to the VSC in use
EMi
Minimum value for Variable Speed Compressor (RPM * 10) in Energy Saving
Mode: (0 to EMA) select according to the VSC in use
EMA
Maximum value for Variable Speed Compressor (RPM * 10) in Energy Saving
Mode: (EMi to 500) select according to the VSC in use
Fr0
Value when Variable Speed Compressor is shut down (RPM * 10): (0 to 200) select
according to the VSC in use
tSt
PI regulator, temperature sampling time: (00:00 to 42min:30sec)
iSt
PI regulator, integral sampling time: (00:00 to 42min:30sec)
vdC
Type of Variable Speed Compressor: (nu; FrE) nu = no VSC in use; FrE = VSC with
frequency control mode is used; VC1 = Embraco with serial control; VC2 = SECOP
with serial control.
voS
Signal output variation for Variable Speed Compressor: (0 to 100 Hz or RPM*10)
VSC variation when SET-HY ≤ T ≤ SET+HY
vo2
Signal output variation for Variable Speed Compressor: (0 to 100 Hz or RPM*10;
nu)) VSC variation when SET-HY-HY1≤T<SET-HY and SET+HY<T≤SET+HY+HY1
vo3
Signal output variation for Variable Speed Compressor: (0 to 100 Hz or RPM*10;
nu)) VSC variation when SET-HY-HY1<T and T>SET+HY+HY1
PdP
Variable Speed Compressor (in %) during any Pull Down: (0 to 100%) this value
is always calculated using FMi and FMA limits. 0=function disabled.
SPi
Compressor speed (in %) in case of any probe error during Con interval: (0 to
100%) this value is always calculated using FMi and FMA limits.
Aod
Compressor speed (in %) during any defrost cycle (valid if tdf=in): (0 to 100%)
this value is always calculated using FMi and FMA limits.
AoF
Compressor speed (in%) during a pre-defrost phase (valid if tdf=in): (0 to 100%)
this value is always calculated using FMi and FMA limits.
tHv
PI regulator, max interval for output variation: (tLv to 255 sec)
tLv
PI regulator, min interval for output variation: (1 sec to tHv)
rSr
PI regulator, range for output value calculation (RPM * 10): (0=disabled; 1 to 255
RPM*10)
Str
PI regulator, delay before range drift: (0 to 255 sec)
dPt
PI regulator, divisor for PI response time reduction (acts on both par. tSt and
iSt): (1 to 10)
CMn
Continuous control ON in normal mode: (n; Y) Y = VSC is never stopped during
regulation.
CME
Continuous control ON in energy saving mode: (n; Y) Y = VSC is never stopped
during regulation.
MnP
Compressor speed threshold to activate lubrication (valid for variable speed
compressors only, 0=disabled): (nu; 1 to 100%; OFF) nu = not used; 1 to 100% =
select the percentage to activate function; OFF = compressor is stopped when the
condition is reached
tMi
Time range with compressor speed below MnP to activate lubrication cycle:
(00:00 to 24h00min) time before activating the lubrication function
tMA
Time range with compressor speed at 100% to activate lubrication cycle: (0 to
255 min) VSC will be forced to 100%, for tMA, after activating the lubrication function.
NOTE: if MnP=OFF, VSC will be stopped for tMA
A00
Number of serial controlled VSC: (1 to 2) number of VSC connected
A01
Serial address for compressor 1: (1 to 247)
A02
Serial address for compressor 2: (1 to 247)
VARIABE SPEED FAN (MODBUS) - vSF
S00
Number of serial condenser fans (0=disabled): (0 to 4) number of variable
speed condenser fans controlled via Modbus. Only EMB ventilators are supported.
C01…C04
Serial addresses for condenser fans: (1 to 247) up to 4 condenser fan can be
controlled in parallel (all of them will use the same speed value).
F12
Serial baudrate for condenser fan (kbaud): 4.8=4800baud; 9.6=9600baud;
19.2=19200baud
SFr
Direction of rotation for condenser fan: (Lt; rt) Lt = left rotation; rt = right rotation
tCC
Time with condenser efficiency function activated: (0 to 255 sec) interval for
condenser fans cleaning function.
CdF
Default configuration sent to condenser fan (at power on): (n; Y)
DISPLAY MENU - diS
CF
Temperature measurement unit: (°C; °F) °C = Celsius; °F = Fahrenheit.
rES
Temperature resolution: (dE; in) dE = decimal; in = integer.
rEd
Remote keyboard visualization: (P1; P2; P3; P4; Set; dtr) Px=probe “x”; Set=set
point; dtr=percentage calculated from P1 and P2 and using par. dtr.
dLY
Temperature display delay: (0.0 to 20min00sec, res. 10 sec) when the temperature
increases, the display is updated of 1°C or 1°F after this time.
dtr
Probe visualization percentage, F(P1; P2): (1 to 99) with dtr=1 the display will show
this value VALUE=0.01*P1+0.99*P2
DEFROST MENU - dEF
EdF
Defrost mode: in=fixed intervals; rtC=following real time clock
tdF
Defrost type: EL=electrical heaters; in=hot gas
dFP
Probe selection for defrost control: (nP; P1; P2; P3; P4) nP=no probe; Px=probe
“x”.
dSP
Probe selection for 2
nd
defrost control: (nP; P1; P2; P3; P4) nP=no probe;
Px=probe “x”.
dtE
End defrost temperature: (-55 to 50°C; -67 to 122°F) sets the temperature measured
by the evaporator probe (dFP), which causes the end of defrost cycle.
dtS
End 2
nd
defrost temperature: (-55 to 50°C; -67 to 122°F) sets the temperature
measured by the evaporator probe (dFP), which causes the end of defrost cycle.
idF
Interval between two successive defrost cycles: (0 to 120 hours) determines the
time interval between the beginning of two defrosting cycles.
MdF
Maximum length of defrost cycle: (0 to 255 min; 0 means no defrost) when P2P=n
(no evaporator probe presence) it sets the defrost duration, when P2P=Y (defrost end
based on evaporator temperature) it sets the maximum length for the defrost cycle.
MdS
Maximum length of 2
nd
defrost cycle: (0 to 255 min; 0 means no defrost) when
P2P=n (no evaporator probe presence) it sets the defrost duration, when P2P=Y
(defrost end based on evaporator temperature) it sets the maximum length for the
defrost cycle.
dSd
Start defrost delay: (0 to 255 sec) delay in defrost activation.
StC
Compressor off-cycle before starting any defrost: (0 to 255 sec) interval with
compressor OFF before activating hot gas cycle
dFd
Displaying during defrost: (rt; it; SEt; dEF; Coo) rt = real temperature; it = start
defrost temperature; SEt = set point; dEF = label dEF”; Coo = when a defrost ends,
it shows the label “Coo” until the regulation temperature is above SET+HY+HY1
dAd
Temperature display delay after any defrost cycle: (0 to 255 min) delay before
updating the temperature on the display after the end of any defrost.
Fdt
Draining time: (0 to 120 min) regulation delay after finishing a defrost phase
Hon
Drain heater enabled after draining time (par. Fdt): (0 to 255 min) the relative output
will stay on after draining time.
SAt
Sampling time to calculate the average compressor speed before any desfrost
cycle: (0 to 255 min) the average compressor speed is used only with VSC.
dPo
Defrost cycle enebled at stat-up: (n; Y) enables defrost at power on.
dAF
Pre-defrost time: (0 to 255 min) enable a lower setpoint (SET-1°C or SET-2°F) before
activating the defrost phase.
od1
Automatic defrost (at the beginning of any energy saving mode): (n; Y) n=function
disabled; Y=function enabled
od2
Optimized defrost: (n;Y) n = function disabled; Y = the controller needs a temperature
probe placed on the evaporator surface to monitor the presence of ice during any
defrost phase.
Syd
Type of synchronized defrost: (n; SYn; nSY; rnd) n = function disabled; SYn =
synchronized, all devices connected will start a defrost phase at the same time. nSY
= de-synchronized, all devices connected will delay the beginning of the same defrost
phase; rnd = random defrost function.
dt1
Differential temperature for latent heating control (0.1 to 1.0 °C) to catch the latent
heating phase during any defrost
ndE
Number of connected controllers for special defrost operations (valid if
Syd=SYn, nSY or rnd): (1 to 20) number of devices connected to the same network
for syncro, desyncro or random defrost.
FAN MENU - FAn
FAP
Probe selection for evaporator fan: (nP; P1; P2; P3; P4) nP=no probe; Px=probe “x”.

Related product manuals